08/29/2005 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Denied CITY OF TUCSON DEVELOPMENT SERVICES
STRUCTURAL REVIEW COMMENTS

DATE: 8/26/05
ACTIVITY NUMBER: T05CM00528
PROJECT NAME: Advance America
PROJECT ADDRESS: 105 S. Houghton Rd. #125
ARCHITECT / ENGINEER: Phillip Hawkins
PROJECT REVIEWER: Christy Foreman



TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1108 OR EMAIL AT CFOREMA1@CI.TUCSON.AZ.US IF YOU CARE TO DISCUSS.


1) Provide code analysis per City of Tucson requirements. See Code Analysis form available on City of Tucson website - Commercial permit submittal requirements.
2) Clarify separated or non-separated use see IBC 2003 sections 302.3, 302.3.1, & 302.3.2. Therefore building plan is typically provided clarifying adjacent tenant/ occupancies.
3) A handicap employee and customer shall be provided with a accessible path to the restroom per IBC 2003 section 1109.2.1.4 and see section 404 ANSI A117.1 - 2003.
4) Clarify clear floor space for water closet per ANSI A117.1- 2003 section 604.3.
5) Provide documents that are signed and sealed by Arizona registrant. Seal is not signed. Checked status with Arizona Board of Registrar needs a current license