Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T05CM00528
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/05/2005 | BOB SUBA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 07/18/2005 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Denied | 1) Provide code analysis per City of Tucson requirements to justify seperated / non seperated use and fire rating of demising partitions. 2) Provide valuation for cost of construction. 3)Clarify accessible clearance per section 404 of ANSI A117.1-2003. and dimension door opening. Access into office area and clear floor space for water closet setion 604.3. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 08/26/2005 | BETH GRANT | OUT TO CUSTOMER | Completed |
| 08/26/2005 | SUE REEVES | REJECT SHELF | Completed |