Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T05CM00528
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/16/2005 | JIM EGAN | FIRE | REVIEW | Approved | |
| 03/21/2005 | BOB SUBA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | 1.Provide min. 10 point font size on drawings for the sake of clarity when micro-fish reproduced for our records as well as future records for arch.-engineers-contractors etc. 2.Provide the available fault current at service equipment and at panel location. |
| 04/04/2005 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Denied | 1) Provide code analysis per City of Tucson requirements to justify seperated / non seperated use and fire rating of demising partitions. 2) Provide valuation for cost of construction. 3)Clarify accessible clearance per section 404 of ANSI A117.1-2003. and dimension door opening. |
| 04/05/2005 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 04/05/2005 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 04/06/2005 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Passed | |
| 04/07/2005 | GERRY KOZIOL | WWM | REVIEW | Passed | |
| 04/11/2005 | PAUL MACHADO | ENGINEERING | REVIEW | Approved | |
| 04/14/2005 | PETER MCLAUGHLIN | ZONING | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 06/23/2005 | GBONILL1 | OUT TO CUSTOMER | Completed |
| 06/23/2005 | GBONILL1 | REJECT SHELF | Completed |