Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T05CM00525
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/08/2005 | ANY | ENGINEERING | REVIEW | Approved | |
| 02/08/2005 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 02/08/2005 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Denied | 1) CLARIFICATION FOR CODE ANALYSIS DATA SHT. NON-SEPARATED USE OR SEPARATED USE MOST RESTRICTED USE AND JUSTIFY SQ. FOOTAGE. 2) BACK EXIT DOOR AND RESTROOM FACILITY DOOR CREATE A DANGEROUS EXITING CONDITION. PLEASE MODIFY. |
| 02/08/2005 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 02/08/2005 | PETER MCLAUGHLIN | ZONING | REVIEW | Approved | |
| 02/08/2005 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 02/08/2005 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T05CM00525 DENIED 2/8/05 1. Provide conductor size for AC Ckt. 2. Specify sizing of overcurrent protective device for Panel 170 feeder. 3. Please correct any 1999 NEC references to read "2002", in specifications and any other place where this may apply. |
| 02/15/2005 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 02/15/2005 | JIM EGAN | FIRE | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 02/15/2005 | LISA LESNY | OUT TO CUSTOMER | Completed |