Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T05CM00524
Parcel: 136261300

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T05CM00524
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/08/2005 JIM EGAN FIRE REVIEW Approved
02/08/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
02/08/2005 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Denied 1) CLARIFICATION FOR CODE ANALYSIS DATA SHT. NON-SEPARATED USE OR SEPARATED USE MOST RESTRICTED USE AND JUSTIFY SQ. FOOTAGE.
2) BACK EXIT DOOR AND RESTROOM FACILITY DOOR CREATE A DANGEROUS EXITING CONDITION. PLEASE MODIFY.
02/08/2005 ROBERT SHERRY WATER REVIEW Approved
02/08/2005 PETER MCLAUGHLIN ZONING REVIEW Approved
02/08/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
02/08/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T05CM00524 DENIED 2/8/05
1. Provide conductor size for AC Ckt.
2. Specify sizing of overcurrent protective device for Panel 156 feeder.
3. Please correct any 1999 NEC references to read "2002", in specifications and any other place where this may apply.
02/08/2005 ANY ENGINEERING REVIEW Approved
02/15/2005 GERRY KOZIOL WWM REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
02/15/2005 LISA LESNY OUT TO CUSTOMER Completed