Permit Number: T05CM00522
Parcel: 12402024A

Review Status: Completed

Review Details: REVISION

Permit Number - T05CM00522
Review Name: REVISION
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/15/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Revise the sizes of the water piping based on the submitted water calculations.
2. The minimum slope for waste lines smaller than 4" is 1/4" per foot.
3. The two-way cleanout shown on the floor plan (but not on the riser diagram) only needs to be a one-way cleanout due to the 4" clean out at the upper terminal.
4. Show the revised venting of the floor sink located at the north end of the waste system.