Permit Review Detail
Review Status: Completed
Review Details: RESIDENTIAL BLDG/WWM
Permit Number - T05CM00519
Review Name: RESIDENTIAL BLDG/WWM
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/22/2005 | DAVE WITT | BUILDING-RESIDENTIAL | REVIEW | Approved | PLAN CHECK COMMENTS - PROJECT #T05CM00519 3/22/05 7486 E. RIO VISTA CIR. PLAN REVIEW FOR THE ABOVE REFERENCED STRUCTURE HAS BEEN COMPLETED. THIS LETTER REFLECTS COMMENTS TO BE ADDRESSED. IN ORDER TO FACILITATE A SHORTER BACK CHECK TIME, WE REQUEST THAT YOU PLEASE PROVIDE REVISED PLANS AND CALCULATIONS, HIGHLIGHTING ANY CHANGES, ALONG WITH A WRITTEN RESPONSE TO EACH OF THE NOTED ITEMS INDICATING ACTION TAKEN. SCOPE OF REVIEW: THE SCOPE OF THIS PLAN REVIEW COVERS ARCHITECTURAL, PLUMBING, MECHANICAL, MODEL ENERGY AND ELECTRICAL CODES. ALL CODE REFERENCES ARE TO THE 2003 IRC AND STATE PLUMBING CODE. ALL FEATURES WERE CHECKED ONLY TO THE EXTENT ALLOWED BY THE SUBMITTALS PROVIDED. ALL PORTIONS OF THIS PROJECT ARE ASSUMED TO MEET OR WILL MEET OTHER DEPARTMENTAL REQUIREMENTS, CONDITIONS AND CONCERNS BEFORE PERMIT APPROVAL. GENERAL REQUIREMENTS: 1. ALL PLANS SHALL BE LEGIBLE AND A SCALE NO SMALLER THAN ΒΌ INCH = 1-FOOT SHALL BE USED FOR ALL FLOOR PLANS, FRAMING PLANS AND ELEVATIONS. DETAILS &CROSS SECTIONS AT A MINIMUM 3/8 INCH = 1-FOOT SCALE. 2. ALL CORRECTIONS AND REVISIONS SHALL BE MADE ON THE ORIGINAL TRACINGS AND TWO NEW SETS OF PRINTS OR (1) SEPIA & (1) BLUE LINE SHALL BE RETURNED ALONG WITH ALL REDLINE PRINTS. 3. PEN OR PENCIL CORRECTIONS ON FINAL PRINTS WILL NOT BE ACCEPTABLE. TO AVOID DELAYS ENSURE ALL CORRECTIONS HAVE BEEN MADE, ARE COMPLETE AND HAVE BEEN COORDINATED ON ALL APPLICABLE DETAILS AND NOTES. STRUCTURAL PLANS: 1. ROOF FRAMING / 3 ; THE 2-2X6 HEADER APPEARS INADEQUATE FOR THE 5040 IN THE MASTER BEDROOM. PLEASE JUSTIFY. 2. ROOF FRAMING / 3 ; THE 4X6 BEAM OVER THE 5'-2" SPAN OVER THE ENTRY APPEARS INADEQUATE. PLEASE JUSTIFY. 3. ROOF FRAMING / 3 ; THE 2-2X8 HEADER OVER THE 8068 IN THE LIVING ROOM APPEARS INADEQUATE. PLEASE JUSTIFY. 4. PROVIDE MANUFACTURER'S CALCULATIONS AND DATA FOR PRE-FAB TRUSSES. TRUSS CALCULATIONS MUST BE SIGNED, DATED AND WET-SEALED BY AN ENGINEER WHO IS REGISTERED IN ARIZONA. TRUSS CALCULATIONS SHALL BE CROSS-REFERENCED TO THE FLOOR PLANS. DEFERRED SUBMITTAL? 5. SPECIFY AND DETAIL ALL OVER FRAMING. IF SOLID SHEATHING IS USED ON THE LOWER TRUSSES, PROVIDE MINIMUM OPENINGS OF 22" BY 30" FOR ACCESS AND VENTILATION INTO OVER FRAMED AREAS (>30 S.F.). IF SOLID SHEATHING IS NOT USED ON LOWER TRUSSES, PROVIDE DETAILS FOR BRACING OF TOP CHORD OF LOWER TRUSSES. ELEVATIONS: 1. NORTH ELEVATION / 4 ; THE DESCRIPTION OF THE CARPORT BEAM DIFFERS FROM THE BEAM ON THE FRAMING PLAN. PLEASE CO-ORDINATE. SECTIONS - DETAILS - MISC. NOTES: 1. SECTION B-B / 4 , 1/5 ; HOW DOES THE GWB ON THE CEILING FRAMED AT 24" O.C. COMPLY WITH TABLE R702.3.5 FOOTNOTE D? 2. 2 / 5 ; JUSTIFY THE 3-16d, INTO END GRAIN OF TRUSS,LEDGER CONNECTION. NDS 12.2.2 AND NDS TABLE 12.3A . I'M USING A 1991 NDS, IS IT STILL VALID? 3. 3 / 5 ; THE SUPERIOR FIRE PLACE BRF42 FIRE BOX OPENING IS OVER 6 SQ.FT. PLEASE RECONSIDER THE HEARTH DIMENSION. SEE R1003.10 . 4. STRUCTURAL SPECIFICATIONS / 5 ; PLEASE UPDATE THE NOTES ABOUT THE 2OOO IRC TO 2003 IRC. PLUMBING PLANS: 1. NOTE ON PLAN COMPLIANCE WITH WATER CONSERVATION; WATER CLOSETS 1.6 GALLONS PER FLUSH, SINKS AND SHOWERHEADS 3 GALLONS PER MINUTE. ELECTRICAL PLANS: 1. PLEASE PROVIDE ARC FAULT PROTECTION FOR THE BEDROOM RECEPTACLES. SEE E3802.11 . IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT YOUR ASSIGNED PLANS EXAMINER: DAVE WITT @ 791-5550 EXT. 1110 |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 03/23/2005 | CINDY AGUILAR | OUT TO CUSTOMER | Completed |
| 03/23/2005 | ANGIE SHOFFSTALL | REJECT SHELF | Completed |