Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T05CM00511
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/01/2005 | DAVE WITT | BUILDING-RESIDENTIAL | REVIEW | Denied | PLAN CHECK COMMENTS - PROJECT #T05CM00511 7/6/05 3348 N. FORGEUS AVE. PLAN REVIEW FOR THE ABOVE REFERENCED STRUCTURE HAS BEEN COMPLETED. THIS LETTER REFLECTS COMMENTS TO BE ADDRESSED. IN ORDER TO FACILITATE A SHORTER BACK CHECK TIME, WE REQUEST THAT YOU PLEASE PROVIDE REVISED PLANS AND CALCULATIONS, HIGHLIGHTING ANY CHANGES, ALONG WITH A WRITTEN RESPONSE TO EACH OF THE NOTED ITEMS INDICATING ACTION TAKEN. SCOPE OF REVIEW: THE SCOPE OF THIS PLAN REVIEW COVERS ARCHITECTURAL, PLUMBING, MECHANICAL, MODEL ENERGY AND ELECTRICAL CODES. ALL CODE REFERENCES ARE TO THE 2000 IRC AND STATE PLUMBING CODE. ALL FEATURES WERE CHECKED ONLY TO THE EXTENT ALLOWED BY THE SUBMITTALS PROVIDED. ALL PORTIONS OF THIS PROJECT ARE ASSUMED TO MEET OR WILL MEET OTHER DEPARTMENTAL REQUIREMENTS, CONDITIONS AND CONCERNS BEFORE PERMIT APPROVAL. GENERAL REQUIREMENTS: 1. ALL PLANS SHALL BE LEGIBLE AND A SCALE NO SMALLER THAN ΒΌ INCH = 1-FOOT SHALL BE USED FOR ALL FLOOR PLANS, FRAMING PLANS AND ELEVATIONS. DETAILS &CROSS SECTIONS AT A MINIMUM 3/8 INCH = 1-FOOT SCALE. 2. ALL CORRECTIONS AND REVISIONS SHALL BE MADE ON THE ORIGINAL TRACINGS AND TWO NEW SETS OF PRINTS OR (1) SEPIA & (1) BLUE LINE SHALL BE RETURNED ALONG WITH ALL REDLINE PRINTS. 3. PEN OR PENCIL CORRECTIONS ON FINAL PRINTS WILL NOT BE ACCEPTABLE. TO AVOID DELAYS ENSURE ALL CORRECTIONS HAVE BEEN MADE, ARE COMPLETE AND HAVE BEEN COORDINATED ON ALL APPLICABLE DETAILS AND NOTES. FOUNDATION: 1. PLEASE PROVIDE A LANDING OUTSIDE THE EXTERIOR DOOR TO THE GREAT ROOM. SEE R 311.4.3 . 2. ALL FOUNDATION HOLD-DOWNS AND ANCHOR BOLT SPACING FOR SHEAR WALLS SHALL BE SPECIFIED AND LOCATED. HOW DOES THE WEST WALL OF THIS PROJECT COMPLY WITH R 602.10 ? FLOOR PLANS: 1. PLEASE ADD A NOTE BRACING THE 1 5/8" FURRING AT MID-SPAN OR JUSTIFY THE DEFLECTION. 2. PROVIDE ACCESS TO EACH SEPARATE ATTIC AND CRAWL SPACE THAT EXCEEDS 30SF. DESIGNATE LOCATIONS ON THE DRAWINGS. OPENINGS SHALL NOT BE LESS THAN 22" BY 30". THE ATTIC ACCESS SHALL PROVIDE A MINIMUM OF 30" OF HEADROOM, AND SHALL BE LOCATED IN A HALLWAY OR READILY ACCESSIBLE SPACE PER R807. 3. NOTE THAT THE SHOWER ENCLOSURE SHALL BE FINISHED WITH CERAMIC TILE, OR A LISTED ENCLOSURE, TO A HEIGHT OF 72" ABOVE THE DRAIN PER R702.4 AND R307.2 4. LOCATE AND IDENTIFY SHEAR WALL TYPES AND LOCATIONS. PROVIDE NAILING SCHEDULE. SEE R602 . STRUCTURAL PLANS: 1. SPECIFY DESIGN CRITERIA ON PLANS. VALUES FOR FLOOR DEAD LOAD AND LIVE LOAD, ROOF DEAD LOAD AND LIVE LOAD. 2. SPECIFY LUMBER GRADE AND SPECIES. 3. SPECIFY AND DETAIL ALL OVER FRAMING. IF SOLID SHEATHING IS USED ON THE LOWER TRUSSES, PROVIDE MINIMUM OPENINGS OF 22" BY 30" FOR ACCESS AND VENTILATION INTO OVER FRAMED AREAS (>30 S.F.). IF SOLID SHEATHING IS NOT USED ON LOWER TRUSSES, PROVIDE DETAILS FOR BRACING OF TOP CHORD OF LOWER TRUSSES. 4. PROVIDE A PLATE UNDER THE POINT LOADS OF THE ROOF'S OVER FRAME'S RAFTERS. SECTIONS - DETAILS - MISC. NOTES: 1. C, D, SECTION 2 / 2 ; HOW DOES THE CEILING DRYWALL COMPLY WITH TABLE R702.3.5 FOOTNOTE D ? 2. D / 2 ; PLEASE DESCRIBE THE TRUSS / RAFTER CONNECTION. SEE TABLE R602.3 (1) . 3. D / 2 ; PLEASE DESCRIBE THE TRUSS / PLATE CONNECTION . 4. A, B / 2 ; PROVIDE WEEP HOLES AT THE BASE OF THE VENEER. SEE R703.7.6 . 5. A, B / 2 ; PLEASE DIMENSION THE DEPTH OF THE FOOTING BELOW NATURAL GRADE. SEE R403.1.4 . 6. PLEASE PROVIDE A CROSS SECTION OF A TYPICAL INTERIOR PARTITION. PLUMBING PLANS: 1. NOTE AND SPECIFY ALL PIPING MATERIALS. 2. THE FIXTURE UNITS CONFLICT WITH THE UNIFORM PLUMBING CODE'S TABLE 6-3. IN ORDER TO USE THE PLUMBING FROM THE INTERNATIONAL CODES, AN APPEAL TO THE BUILDING OFFICIAL IS REQUIRED TO BE APPROVED. ELECTRICAL PLANS: 1. THE RECEPTACLES APPEAR TO BE OVER SPACED TO THE LEFT OF THE KITCHEN SINK. SEE E3801.4.1 . 2. PROVIDE ARC FAULT PROTECTION FOR THE RECEPTACLES IN THE BED ROOMS. SEE E3802.11 . 3. WHERE CEILING FANS ARE SHOWN ON THE PLANS, PROVIDE A NOTE INDICATING ONLY APPROVED OUTLET BOXES SHALL BE USED, PER E4001.6. 4. NOTE THAT LIGHT FIXTURES IN CLOTHES CLOSETS SHALL BE INSTALLED IN ACCORDANCE WITH E3903.11. 5. CLARIFY THE LOCATION AND ACCESS TO THE SUB-PANEL. IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT YOUR ASSIGNED PLANS EXAMINER: DAVE WITT @ 791-5550 EXT. 1110 |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 07/08/2005 | CINDY AGUILAR | OUT TO CUSTOMER | Completed |
| 07/08/2005 | ANGIE SHOFFSTALL | REJECT SHELF | Completed |