Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T05CM00502
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/07/2005 | JIM EGAN | FIRE | REVIEW | Approved | |
| 02/07/2005 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Revise the size of the CW lines to the water closets to coordinate with the provided calculations. 2. Indicate the installed height of the water heater. Reference Section 511.2, UPC 1994. 3. Revise detail 2/P.1 to coordinate the termination of the T&P relief with the plumbing plan. 4. Show how the water heater is to be attached to the wall and indicate the construction of the wall to which it is to be attached. |
| 02/07/2005 | RAUL PALMA | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 02/07/2005 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 02/07/2005 | PATRICIA GILBERT | ENGINEERING | REVIEW | Approved | |
| 02/07/2005 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Revise the ventilation of the restrooms to prevent the air in the restrooms from being recirculated. Reference Section 403, IMC 2000. |
| 02/07/2005 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T05CM00502 DENIED 2/7/05 1. WH is listed as 2000W 120V on p.1. Is 4500W 240V on E.1. Coordinate with Mechanical and clarify. 2. There are two AC units on Power Plan B-2,4. There is an AC unit on Panel schedule B-1,3, but none on plans. Pls clarify. 2. #3 CU feeder to Panel B is of ampacity 100A. This would be fine except that it does not appear that the panel load calculations take into account 25% of the largest motor. Please revisit panel load calculations and increase conductor size as necessary. |
| 02/07/2005 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 02/08/2005 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 02/09/2005 | LISA LESNY | OUT TO CUSTOMER | Completed |