Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T05CM00486
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/04/2005 | JIM EGAN | FIRE | REVIEW | Approved | |
| 02/04/2005 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 02/04/2005 | PATRICIA GILBERT | ENGINEERING | REVIEW | Approved | |
| 02/04/2005 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 02/04/2005 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 02/08/2005 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 02/08/2005 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 02/16/2005 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | T05CM00486 DENIED 2/8/05 1. Put on Panel Schedule: receptacles on NE corner. 2. WH-2 is 120V on Sheet P-1, powered at 208V on Sheet E-1. Coordinate with Plumbing and clarify. 3. EGC in Panel B feeder should be #6, not #8. Reference NEC Table 250.122. 4. Provide fault calculations for AFC at Panel B. 5. Provide 2000 IECC Lighting Power Budget calculatio |
| 02/17/2005 | PETER MCLAUGHLIN | ZONING | REVIEW | Approved |