Permit Number: T05CM00486
Parcel: 141185820

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T05CM00486
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/04/2005 JIM EGAN FIRE REVIEW Approved
02/04/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
02/04/2005 PATRICIA GILBERT ENGINEERING REVIEW Approved
02/04/2005 ROBERT SHERRY WATER REVIEW Approved
02/04/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
02/08/2005 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Approved
02/08/2005 GERRY KOZIOL WWM REVIEW Approved
02/16/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved T05CM00486 DENIED 2/8/05
1. Put on Panel Schedule: receptacles on NE corner.
2. WH-2 is 120V on Sheet P-1, powered at 208V on Sheet E-1. Coordinate with Plumbing and clarify.
3. EGC in Panel B feeder should be #6, not #8. Reference NEC Table 250.122.
4. Provide fault calculations for AFC at Panel B.
5. Provide 2000 IECC Lighting Power Budget calculatio
02/17/2005 PETER MCLAUGHLIN ZONING REVIEW Approved