Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T05CM00462
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
02/03/2005 | JIM EGAN | FIRE | REVIEW | Approved | |
02/03/2005 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Denied | 1) PROVIDE CLARIFICATION / STRUCTURAL CALCULATIONS FOR NEW POST AND GLULAM BEAM. 2) RESTROOM FACILITY NEEDS TO BE PER ANSI A117.1 2003 STANDARDS OR 20% COST OF CONSTRUCTION NEEDS TO BE SPENT TOWARDS MEETING THE REQUIREMENTS. JUSTIFY WITH NUMBERS AND MODIFICATIONS. 3) CLARIFY REMOVAL OF PARTITIONS OR ADDED OPENINGS ARE IN NON-BEARING WALLS OR JUSTIFY WITH STRUCTURAL CALCULATIONS. |
02/03/2005 | DAN CASTRO | ZONING | REVIEW | Approved | |
02/03/2005 | BLANCA ESPINO | ENGINEERING | REVIEW | Approved | |
02/04/2005 | LLESNY1 | PLUMBING-COMMERCIAL | REVIEW | Needs Review | |
02/04/2005 | LLESNY1 | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review | |
02/04/2005 | LLESNY1 | WWM | REVIEW | Needs Review | |
02/04/2005 | LLESNY1 | MECHANICAL-COMMERCIAL | REVIEW | Needs Review | |
02/04/2005 | LLESNY1 | WATER | REVIEW | Needs Review |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
02/04/2005 | LISA LESNY | OUT TO CUSTOMER | Completed |