Permit Number: T05CM00456
Parcel: 107010550

Review Status: Completed

Review Details: RESIDENTIAL BLDG/ZONING/NPPO

Permit Number - T05CM00456
Review Name: RESIDENTIAL BLDG/ZONING/NPPO
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/02/2005 DAVID BELL LANDFILL REVIEW Approved
02/07/2005 ANDREW CONNOR NPPO REVIEW Passed
03/04/2005 PETER MCLAUGHLIN ZONING REVIEW Denied BOARD OF ADJUST MENT VARIANCE COMMENTS

FROM: Peter McLaughlin
Senior Planner-Zoning Review
Development Services Dept.


SUBJECT PROPERTY:
Additions at 517 W. Gretchen Drive
TRANSMITTAL: March 4, 2005


COMMENTS: Please attach a response letter with the next submittal, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.

1. It is unclear why a 10-foot perimeter building setback is shown when only one unit is stated to exist on the property. Please clarify. If one one unit exists on the site, in the MH-1 zone, the required bldg. setback is the greater of 6 feet and 2/3 height of exterior structure wall. Revise setback dimension accordingly. Also, specify the height of the doghouse on the site plan in order to verify setbacks.
LUC 3.2.6.4
DS 2-02.2.1.A.7

2. A minimum setback of 18 feet is required between a garage and street property line (and 19 feet between garage and back of sidewalk) per LUC 3.2.6.5.B.2. Also, minimum street perimeter yard setback for the proposed residences is required to be the great of 20 feet or 1 ½ times the height of exterior building wall measured from property line. A zero-foot (0') street perimeter yard setback is proposed for both the new residence and their garages along S. Meyer Ave. A BOA Variance is required. Place the variance case number, date of approval, variances approved and conditions on the plan.
LUC 3.2.6.5

If you have any questions about this transmittal, please call Peter McLaughlin, (520) 791-5608.
03/07/2005 NEAL SAUNDERS BUILDING-RESIDENTIAL REVIEW Denied Plan Check Comments - Project T05cm00456

Plan Review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, highlighting any changes, along with a written response to each of the noted items indicating action taken.

General Requirements

1. All corrections and revisions shall be made on the original tracings and two new sets of prints or (1) sepia and (1) blue line shall be returned.
2. Pen or pencil corrections on final prints will not be acceptable. To avoid delays ensure that corrections have been made, are complete and have been coordinated on all-applicable details and notes.

Site Plan

1. Proximity to property line will require west wall of structure to have a 1-hour rated wall. Provide.
2. FYI - Zoning may have other issues with this plan.

Structural Plan

1. Specify slope and roofing of doghouse roof.
2. Specify roof deck screw pattern.
3. Epoxy bolts require special inspection. Submit form.

Electrical Plan

1. Provide ground for garage sub-panel.

If you have any questions, please contact your assigned plans examiner Neil Saunders at 791-5550, extension 1113.

Final Status

Task End Date Reviewer's Name Type of Review Description
03/08/2005 CINDY AGUILAR OUT TO CUSTOMER Completed
03/08/2005 ANGIE SHOFFSTALL REJECT SHELF Completed