Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T05CM00421
Parcel: 11007232A

Address:
4067 E GRANT RD

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T05CM00421
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/07/2005 JIM EGAN FIRE REVIEW Approved
02/08/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Provide calculations to show that the common ventilation systems for AC-7 and AC-8 are sized in accordance with Section 403.3.2, IMC 2000.
02/08/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Clarify the note regarding the installation and operation of the Taco "D'MAND" hot water pump and provide a detail showing the installation.
2. Provide information to show that the installation of the ¾" CW and ¾" HW piping for the new sink will not overload the existing ¾" CW and ¾" HW piping to which they are to be attached.
3. Show how the revised hot water system complies with Section 804.5, IECC 2000.
4. Show how the proposed sump pump installation complies with the requirements of Sections 710.4, 710.5, and 710.10, UPC 1994.
02/08/2005 ROBERT SHERRY WATER REVIEW Approved
02/16/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov
IF YOU CARE TO DISCUSS.

1. Please note that ASHRAE Table 9.3.1.2, as revised 5/8/03, allows 1.1 W/SF for Offices. Using this criteria would not allow the installation of lighting as designed. However, City of Tucson allows the use of the 2000 IECC, which per Table 805.4.2 allows 1.5 W/SF for Offices. This appears to bring the total allowed Lighting Power below that which is proposed to be installed.
2. Please add 25% for continuous loading for lights on Panel LA, also on Panel AC as necessary. Total must not exceed ampacity of Service Entrance Conductors, (2) 500 KCMIL, or 760A.
3. Please provide a disconnect for the Water Heater per NEC 422 Part III, or justify otherwise.
03/08/2005 RAUL PALMA BUILDING-COMMERCIAL REVIEW Denied City of Tucson, Development Services
BUILDING AND STRUCTURAL COMMENTS

1) Rooms 206 and 207 seem like a curtain wall will divide them. How is this
curtain wall to be connected at roof? Will it be hung from the roof? Show details
and provide calc`s.
03/14/2005 GERRY KOZIOL WWM REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
03/18/2005 BETH GRANT OUT TO CUSTOMER Completed
03/18/2005 SUE REEVES REJECT SHELF Completed