Review Details: RESUBMITTAL
Permit Number - T05CM00409
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/01/2005 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 04/15/2005 | NEAL SAUNDERS | BUILDING-RESIDENTIAL | REVIEW | Denied | 1. Minimum default values on MEC's means nothing unless you can show 15% or less glazing per N1102.1. If this is possible then follow table N1102.1 (HDD=2100, zone 5). If this is not possible submit MEC calcs to support chosen values - per chapters 4&5 2000 IECC or 'Rescheck' (DOE website). 2. Elevations still show shingles on roof. 3.Specify and detail all over-framing. If solid sheathing is used on the lower trusses, provide minimum openings of 22" by 30" for access and ventilation into over-framed areas (>30 S.F.). If solid sheathing is not used on lower trusses, provide details for bracing of top chord of lower trusses. 4. Check with Southwest Gas for mater placement under porch. 5. Provide combustion and relef vents for water heater in Garage per AZ state plumbing code or Chapter 17, 2003 IRC. Call Neil Saunders @ 791-5550 x113 for any questions |