Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T05CM00401
Parcel: 11704226A

Address:
510 N STONE AV

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T05CM00401
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/04/2005 PATRICIA GILBERT ENGINEERING REVIEW Denied DATE: October 4, 2005
ACTIVITY NUMBER: T05OT00736/T05CM00401
PROJECT NAME: Tenant Improvement
PROJECT ADDRESS: 510 North Stone Ave.
PROJECT REVIEWER: Patricia Gilbert

FLOODPLAIN USE PERMIT IS DENIED
SITE PLAN IS DENIED

RESUBMITTAL REQUIRED: SITE PLAN, CONTRACTOR'S ESTIMATE, 2005 PIMA COUNTY ASSESSOR'S RECORD OR APPRAISAL FROM A LICENSED APPRAISER, FLOODPLAIN USE PERMIT APPLICATION

1. This structure was built prior to 1982 when the Floodplain Ordinance came into effect. The structure is considered a non-conforming structure within a FEMA Flood Hazard Area, Zone AE. If the cost of improvements or repairs is 50% or less of the current market value of the structure it is considered a non-substantial improvement. The value of the structure and a contractor's estimate is required to determine if the improvements are less than 50%. Submit a contractor's estimate of the proposed work, labor and materials and the 2005 Pima County Assessor's Record (value of structure).
10/31/2005 RAUL PALMA BUILDING-COMMERCIAL REVIEW Denied City of Tucson, Development Services
BUILDING AND STRUCTURAL COMMENTS
04/19/05

1) Provide the engineers seal on the structural sheets.
2) Provide engineering calc`s for the lintel at the overhead door.
3) Provide engineering for the roof members for any equipement on the roof.
4) Provide a phy. Handicapped bathroom. Show all details.
5) Building shall be made accessible to the Phy. Handicapped.
6) Is upper level existing? If so indicate on plans.
7) Specify the uses and occupancy(s) group of the building. It appears like
there is more than one occupancy or use. Clarify!


10/27/05

1) Provide connection details for grab bars to wall.
2) section 303.3 of the 2003 ANSI standards the physically handicapped
specifies that any changes in level greater then ¼" in height but less then
½" shall be beveled.
3) Egress from a room or space shall not pass through adjoining or intervening
rooms. Section 1013.
4) Identify on plans as to which are the partitions and which are the trusses.
5) Ground level floor plan shows a beam, truss. or wall being removed, specify
what it is.
6) Are the spaces above shown as offices existing office spaces? Varify!
7) Specify width of exit door leading to physically handicapped bathroom, and
also exiting out of the building.
8) Are all overhead doors exiting?

Final Status

Task End Date Reviewer's Name Type of Review Description
11/08/2005 CINDY AGUILAR OUT TO CUSTOMER Completed
11/08/2005 SUE REEVES REJECT SHELF Completed