Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 1ST
Permit Number - T05CM00366
Review Name: REVISION - - 1ST
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/03/2007 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T05CM00366 8/3/07 1. Specify revised wiring method with resoect to original approved drawings. 2. Demonstrate compliance with NEC 225.10, Wiring on Buildings. Wiring shall not enter building to power electrical loads exterior to that building. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 08/10/2007 | GERARDO BONILLA | OUT TO CUSTOMER | Completed |