Permit Number: T05CM00305
Parcel: 126071330

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T05CM00305
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/09/2005 NEAL SAUNDERS BUILDING-RESIDENTIAL REVIEW Denied Plan Check Comments - Project T05cm00305

Plan Review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, highlighting any changes, along with a written response to each of the noted items indicating action taken.

General Requirements

1. All corrections and revisions shall be made on the original tracings and two new sets of prints or (1) sepia and (1) blue line shall be returned.
2. Pen or pencil corrections on final prints will not be acceptable. To avoid delays ensure that corrections have been made, are complete and have been coordinated on all-applicable details and notes.

Floor Plan

1. Provide landings at all exterior doors per R311. South entrance to master bedroom.

Structural Plan - All these comments were on the original review yet they were not addressed. I am stil unclear how the new roof will interface with the two existing roofs (shed and House).

1. Callout sizes and connection of all nailers. This is a detail of the non-bearing wall at the roof line. The roof diapraghm must be completed. detail how.
2. Detail how new roof will connect to existing shed roof/wall. Srecify ledger and its connection. This was called out as detail 2 which is unclear. Will the new roof slope continue into the shed roof slope?
3. Detail new roof connection to existing house walls or roofs. Specify ledger and its connection. This was called out as detail 5 but this detail does not exist. Will the house roof slope continue into the new roof slope?

MODEL ENERGY CODE:

1. Call out the "U" values of the windows and doors in compliance with the energy calculations provided.

If you have any questions, please contact your assigned plans examiner Neil Saunders at 791-5550, extension 1113.

NOTE: As of 09/06/04 the City of Tucson has adopted the 2003 IRC with the exception of the plumbing portion which has been replaced with the Arizona state plumbing code. All model plans shall reference these codes. Some 2000 refrences are still present.

Final Status