Permit Number: T05CM00282
Parcel: 11014015A

Review Status: Completed

Review Details: OTHER

Permit Number - T05CM00282
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/24/2005 JIM EGAN FIRE REVIEW Approved See comments on plans.
02/01/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
02/01/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Needs Review
02/01/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
02/04/2005 ANY BUILDING-COMMERCIAL REVIEW Denied S1. AS PREVIOUSLY DISCUSSED, PROVIDE ONE HOUR SEPARATION BETWEEN H4 GAS ROOM AND F2 WTAER PROCESSING ROOM
1. PROVIDE DETAILS OF CONSTRUCTION FOR ONE-HOUR FIRE RATED WALLS SEPARATING GAS ROOM FROM EQUIPMENT AREA.
2. PROVIDE DETAILS FOR ONE-HOUR CEILING AT GAS ROOM.
3. PROVIDE JUSTIFICATION FOR FIRE-RATINGS OF 1 AND 2 ABOVE, LISTING ON DRAWINGS.
S2. REVISE CODE REVIEW CHECKLIST ON DRAWING T-1.
S3. PROVIDE REVISED CONSTRUCTION DETAILS ADDRESSING CONNECTIONS .

Final Status

Task End Date Reviewer's Name Type of Review Description
02/09/2005 LISA LESNY OUT TO CUSTOMER Completed