Permit Number: T05CM00249
Parcel: 128102940

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T05CM00249
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/20/2005 JIM EGAN FIRE REVIEW Approved
01/20/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
01/20/2005 RAUL PALMA BUILDING-COMMERCIAL REVIEW Approved
01/20/2005 ROBERT SHERRY WATER REVIEW Approved
01/20/2005 DAN CASTRO ZONING REVIEW Approved
01/20/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
01/20/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T05CM00249 DENIED 1/20/05
1. Please add new loads from Power Plan IS-17, IS-15, and LV-25 to panel schedules. Then Electrical Plans Examiner will evaluate feeders.
2. It appears that the secondary of X'FMR UPS, with 3/0 conductors, should have #4 GNDs, not #6.
01/20/2005 PATRICIA GILBERT ENGINEERING REVIEW Approved
01/25/2005 GERRY KOZIOL WWM REVIEW Passed

Final Status

Task End Date Reviewer's Name Type of Review Description
01/25/2005 TAMI ACHONG OUT TO CUSTOMER Completed