Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T05CM00249
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/20/2005 | JIM EGAN | FIRE | REVIEW | Approved | |
| 01/20/2005 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 01/20/2005 | RAUL PALMA | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 01/20/2005 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 01/20/2005 | DAN CASTRO | ZONING | REVIEW | Approved | |
| 01/20/2005 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 01/20/2005 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T05CM00249 DENIED 1/20/05 1. Please add new loads from Power Plan IS-17, IS-15, and LV-25 to panel schedules. Then Electrical Plans Examiner will evaluate feeders. 2. It appears that the secondary of X'FMR UPS, with 3/0 conductors, should have #4 GNDs, not #6. |
| 01/20/2005 | PATRICIA GILBERT | ENGINEERING | REVIEW | Approved | |
| 01/25/2005 | GERRY KOZIOL | WWM | REVIEW | Passed |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 01/25/2005 | TAMI ACHONG | OUT TO CUSTOMER | Completed |