Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T05CM00246
Parcel: 117050020

Address:
400 N 2ND AV

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T05CM00246
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/23/2005 PATRICIA GILBERT ENGINEERING REVIEW Denied The proposed platform is impacted by the regulatory floodplain. The floodplain 100-year water surface elevation (WSE) just upstream of the proposed structure is 2387.00 feet. The platform must be elevated above the floodplain 100-year WSE. This can be achieved by either building up the building pad to the 100-year WSE or higher, or elevating the platform by any other acceptable method such as stem walls, piers, etc, depending on what the drainage report, the engineer or the owner is proposing. The structure lowest finish floor, utilities, machinery, equipment (i.e. furnaces, water heaters, heat pumps, air conditioners and their associated equipment, including all electrical equipment), or an open utility platform that provides utility services for the structure on this property, under this permit shall, be placed at a minimum of 2388.00(1 foot above 2387.00) feet above see level, NGVD 1929 as certified by a Registered Land Surveyor.

Indicate the required FFE on the site plan.
09/13/2005 JMORALE1 BUILDING-COMMERCIAL REVIEW Needs Review