Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 1ST
Permit Number - T05CM00246
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
12/04/2006 | LEERAY HANLY | BUILDING-COMMERCIAL | REVIEW | Denied | 1) SEE NOTE 2 FROM 10-19-06. "PROVIDE SPECIFICATIONS FOR CONNECTIONS OF EXISTING LIGHT FIXTURES TO POLE." YOU NEED TO SPECIFY SIZE AND TYPE OF PLATFORM GAINS/CONNECTORS; ANCHORS FOR GAINS/CONNECTORS; SIZE AND TYPE OF WELD AT FRONT GAIN/CONNECTOR. 2) SEE NOTE 3 FROM 10-19-06 "CLARIFY / SPECIFY / JUSTIFY WELDS." PLEASE PROVIDE SIZE AND TYPE OF WELDS FOR LADDER LUGS AND SIZE AND TYPE OF WELDS FOR TUBE STEEL FENCE. 3) PLEASE PROVIDE TYPE AND SPECIFICATIONS FOR COLLAR TIES FOR ANTENNA MOUNTING. THE SHOP DRAWINGS FOR MOUNTS ARE NOT IN THE RESUBMITTED SET. |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
12/21/2006 | CINDY AGUILAR | OUT TO CUSTOMER | Completed |
12/21/2006 | SUE REEVES | REJECT SHELF | Completed |