Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T05CM00226
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
03/02/2005 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Show that access is provided to the water heater located above the ceiling (greater than 8'-0" AFF per detail 10/A5.0). Reference Section 511.2, UPC 1994. 2. The existing floor drain is not an approved termination for the relief valve because it is incapable of containing the discharge without splashing. Reference Section 608.4, UPC 1994. 3. Show how the water piping was sized. Reference Section 610.1, UPC 1994. |
03/04/2005 | DROBEY1 | WWM | REVIEW | Needs Review | |
03/04/2005 | WILDAN | ELECTRICAL-COMMERCIAL | REVIEW | Approved |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
05/04/2005 | BETH GRANT | OUT TO CUSTOMER | Completed |