Review Date Reviewer's Name Type of Review Description Status Comments
03/02/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Show that access is provided to the water heater located above the ceiling (greater than 8'-0" AFF per detail 10/A5.0). Reference Section 511.2, UPC 1994.
2. The existing floor drain is not an approved termination for the relief valve because it is incapable of containing the discharge without splashing. Reference Section 608.4, UPC 1994.
3. Show how the water piping was sized. Reference Section 610.1, UPC 1994.
03/04/2005 DROBEY1 WWM REVIEW Needs Review
03/04/2005 WILDAN ELECTRICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
05/04/2005 BETH GRANT OUT TO CUSTOMER Completed