Permit Number: T05CM00226
Parcel: 10511061R

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T05CM00226
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/19/2005 PATRICIA GILBERT ENGINEERING REVIEW Approved
01/19/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Show that access is provided to the water heater located above the ceiling. Reference Sections 511.2, 511.4, and 511.5, UPC 1994.
2. The safety pan for the water heater is not an approved termination for the relief valve. Reference Section 608.4, UPC 1994.
3. The drain from the water heater safey pan may not terminate at the tailpiece of the lavatory. Reference Section 807.1, UPC 1994.
4. Show how the water piping was sized. Reference Section 610.1, UPC 1994.
01/19/2005 PATRICIA GEHLEN ZONING REVIEW Approved
01/19/2005 ROBERT SHERRY WATER REVIEW Approved
01/19/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
01/20/2005 RAUL PALMA BUILDING-COMMERCIAL REVIEW Approved
01/20/2005 JIM EGAN FIRE REVIEW Approved
01/20/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Needs Review
03/02/2005 EGRANT1 WWM REVIEW Needs Review