Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T05CM00226
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
01/19/2005 | PATRICIA GILBERT | ENGINEERING | REVIEW | Approved | |
01/19/2005 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Show that access is provided to the water heater located above the ceiling. Reference Sections 511.2, 511.4, and 511.5, UPC 1994. 2. The safety pan for the water heater is not an approved termination for the relief valve. Reference Section 608.4, UPC 1994. 3. The drain from the water heater safey pan may not terminate at the tailpiece of the lavatory. Reference Section 807.1, UPC 1994. 4. Show how the water piping was sized. Reference Section 610.1, UPC 1994. |
01/19/2005 | PATRICIA GEHLEN | ZONING | REVIEW | Approved | |
01/19/2005 | ROBERT SHERRY | WATER | REVIEW | Approved | |
01/19/2005 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
01/20/2005 | RAUL PALMA | BUILDING-COMMERCIAL | REVIEW | Approved | |
01/20/2005 | JIM EGAN | FIRE | REVIEW | Approved | |
01/20/2005 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review | |
03/02/2005 | EGRANT1 | WWM | REVIEW | Needs Review |