| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/04/2005 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 02/04/2005 | ANY | BUILDING-COMMERCIAL | REVIEW | Denied | S1. Provide roof plan sealed by structural engineer of record and locating equipment by dimension from two adjacent perimeter walls. S2. Provide site/location plan showing and identifying property lines and location of buildings on property. S3. Provide details for mounting equipment on roof. 2/9/05 Discussed comments #1,2,and 3 with Maher (Mechanical Engineer) at (520) 881-1711. DGL. |
| 02/04/2005 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T05CM00189 DENIED 2/4/05 1. I would question the load counts for largest motor and for the FC circuits. FC circuits pencilled in with proposed load on panel schedule, and would add 144 VA each leg for the 0.6 A motor. This would in aggregate cause a higher service load calculation tally. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 02/16/2005 | TAMI ACHONG | OUT TO CUSTOMER | Completed |