Permit Number: T05CM00189
Parcel: 11206425B

Address:
2525 N TUCSON BL

Review Status: Completed

Review Details: OTHER

Permit Number - T05CM00189
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/21/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Clarify the outside air balancing information; 220 CFM per unit or 220 CFM for each two units?
2. Provide the weights for the condensing units.
3. Show how the building roof complies with the requiremnets of the 2000 IECC.
4. Include the address of the project along with a site plan and a location plan.
5. Provide structural calculations to show that the roof is capable of supporting the new loads.
02/04/2005 EGRANT1 BUILDING-COMMERCIAL REVIEW Needs Review
02/04/2005 EGRANT1 ELECTRICAL-COMMERCIAL REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
02/04/2005 BETH GRANT OUT TO CUSTOMER Completed