Permit Review Detail
Review Status: Completed
Review Details: OTHER
Permit Number - T05CM00189
Review Name: OTHER
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/21/2005 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Clarify the outside air balancing information; 220 CFM per unit or 220 CFM for each two units? 2. Provide the weights for the condensing units. 3. Show how the building roof complies with the requiremnets of the 2000 IECC. 4. Include the address of the project along with a site plan and a location plan. 5. Provide structural calculations to show that the roof is capable of supporting the new loads. |
| 02/04/2005 | EGRANT1 | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
| 02/04/2005 | EGRANT1 | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 02/04/2005 | BETH GRANT | OUT TO CUSTOMER | Completed |