Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T05CM00163
Parcel: 10612199B

Address:
1515 W PRINCE RD

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T05CM00163
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/06/2005 PETER MCLAUGHLIN ZONING REVIEW Approved
05/10/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
05/16/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
06/03/2005 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Denied 1) Please provide code analysis sht. clarifying seperated or non-seperated use. It appears that you are justifying seperated use.
2) Need to show full wall section with rating noted per table 720.1(2) Clarify wall goes to the bottom of the deck..Both detail 4 & 6 are called out on sht. 3. Delete all details not used.
3) Provide indication on floor plan the rated seperation between tenants and provide wall section.
4) Provide note that CMU wall that is to be removed is non-bearing.

Final Status

Task End Date Reviewer's Name Type of Review Description
06/06/2005 KMEDINA1 OUT TO CUSTOMER Completed