Permit Number: T05CM00114
Parcel: 136261300

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T05CM00114
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/08/2005 JIM EGAN FIRE REVIEW Approved
02/08/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied The provided calculations shows that the capacity of the air conditioning equipment exceeds the cooling loads of the project space (load = 13.5 tons vs. capacity of 20 tons). Revise to comply with Section 803.2.1.1, IECC 2000.
02/08/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved
02/08/2005 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Approved R. PALMA OUT ON SICK LEAVE AND CLIENT HERE FROM PHOENIX. I CHECKED PREVIOUS COMMENTS AND CHOSE TO APPROVE IN R. PALMA'S ABSENCE.
02/08/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
02/15/2005 LISA LESNY OUT TO CUSTOMER Completed