Permit Number: T05CM00114
Parcel: 136261300

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T05CM00114
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/11/2005 PATRICIA GILBERT ENGINEERING REVIEW Approved
01/11/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Revise the font size on the drawing to a minimum of 10 points.
2. Provide a riser diagram for the water piping.
3. Provide structural calculations for the water heater support.
4. Show that adequate maintenance access is provided for the water heater. Reference Section 511.4, UPC 1994.
5. Revise the electrical requirements shown for the specified water heater to agree with the Manufacturer's published listing data. Reference Section 301.1.1, UPC 1994.
6. The minimum required water pressure for the specified water closets exceeds the minimum pressure used in the submitted calculations. Revise the calculations as required.
01/11/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied TO5CM00114 DENIED 01/11/05 ELECTRICAL
1. In General Notes on Sheet E3, correct "1999" National Electrical Code to "2002".
2. S.E.S. Load Summary appears to total 1100, not 1081A.
3. Coordinate with Plumbing Review Comment to revise Water Heater power requirements.
01/11/2005 GERRY KOZIOL WWM REVIEW Approved
01/11/2005 DAN CASTRO ZONING REVIEW Approved
01/11/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Revise the font size on the drawing to a minimum of 10 points.
2. Provide calculations to show that the ventilation for the project complies with Section 403, IMC 2000.
3. Provide duct insulation that complies with Section 803.2.8, IECC 2000.
4. Revise the material used for the condensate drain to comply with Section 307.2.2, IMC 2000.
5. Provide calculations to show that the capacity of the air conditioning equipment does not exceed the cooling loads of the project space. Reference Section 803.2.1.1, IECC 2000.
01/11/2005 ROBERT SHERRY WATER REVIEW Approved
02/08/2005 LLESNY1 BUILDING-COMMERCIAL REVIEW Needs Review 1)PROVIDE 2 MEANS OF EGRESS PER TABLE 1014.1 EGRESS SHALL NOT PASS THROUGH ADJOINING ROOMS OR AREAS. SECTION1013.2
2) POST EXIT SIGNS AT ALL EXITS
COMMENTS PER RAUL PALMA
02/08/2005 LLESNY1 FIRE REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
02/08/2005 LISA LESNY OUT TO CUSTOMER Completed