Review Status: Completed

Review Details: POST 3RD PARTY REVIEW

Permit Number - T05CM00105
Review Name: POST 3RD PARTY REVIEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/17/2005 GERRY KOZIOL WWM REVIEW Approved
03/18/2005 ANDREW CONNOR NPPO REVIEW Passed
03/30/2005 HEATHER THRALL ZONING REVIEW Denied DSD TRANSMITTAL

FROM: Heather Thrall Senior Planner FOR: David Rivera Principal Planner

PROJECT: T05CM00105
1236 E. Grant Road
Single Family Residential Bedroom Addition
Site plan
1st Review
Transmittal date: April 1, 2005


COMMENTS: Please resubmit revised drawings along with redlines and a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.

1. Please label the heights of the east and west addition walls on the resubmitted plan. The measurement should be taken from finished grade to top of the parapet.

2. The north setback provided on the submitted site plan indicates the measurement is taken from the north (front) property line. Per the Land Use Code, the street front setback on a major street, such as Grant Road, is taken from the back of the existing curb or future curb location. On the resubmitted site plan, the current and future right of way and curb locations must be shown, with the setback information delineated.

3. Please be aware this project must be developed within future right of way requirements. This residence is required to have a parking area sufficient for two (2) vehicles, and a driveway allowing all vehicular maneuvering to be done on site to ensure vehicles do not back out into Grant Road. The distance on the submitted site plan is only twenty (20) feet between the north property line and the residence, with a notation that ten (10) feet of that area is to be dedicated to the future widening of Grant Road. This information indicates sufficient vehicle use areas will be eliminated with future road widening. The addition will not be permitted to be constructed as shown, as vehicle access and parking will be greatly compromised by the proximity of the unit to the future right of way. A review of the City of Tucson Major Streets and Routes map and parking standards in the Development Standards code indicates you will need approximately 30 feet in front (north) of the residence to allow sufficient parking and vehicle maneuvering on the site.

4. Should you have any questions on this review, please contact me at Heather.Thrall@tucsonaz.gov or at 791-5608x1156.


If you have any questions about this transmittal, please call (520) 791-5608.

Final Status

Task End Date Reviewer's Name Type of Review Description
04/04/2005 CINDY AGUILAR OUT TO CUSTOMER Completed
04/04/2005 ANGIE SHOFFSTALL REJECT SHELF Completed