Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T05CM00048
Review Name: RESUBMITTAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
02/25/2005 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide maintenance access for the water heater. The mounting height of the water heater exceeds 8'-0" AFF for which the code requires a fixed ladder for access to the water heater. Reference Section 511.2, UPC 1994. 2. The floor drain is not an approved location for the termination of the temperature and pressure relief valve because it cannot prevent splashing or flooding. Reference Section 608.5, UPC 1994. 3. The cleanout shown is too small to service the 4" waste line. Reference scection 707.11, UPC 1994. |
03/24/2005 | TACHONG1 | ZONING | REVIEW | Needs Review |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
03/24/2005 | TAMI ACHONG | OUT TO CUSTOMER | Completed |