Permit Number: T05CM00048
Parcel: 10511061R

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T05CM00048
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/25/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide maintenance access for the water heater. The mounting height of the water heater exceeds 8'-0" AFF for which the code requires a fixed ladder for access to the water heater. Reference Section 511.2, UPC 1994.
2. The floor drain is not an approved location for the termination of the temperature and pressure relief valve because it cannot prevent splashing or flooding. Reference Section 608.5, UPC 1994.
3. The cleanout shown is too small to service the 4" waste line. Reference scection 707.11, UPC 1994.
03/24/2005 TACHONG1 ZONING REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
03/24/2005 TAMI ACHONG OUT TO CUSTOMER Completed