Permit Number: T05CM00048
Parcel: 10511061R

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T05CM00048
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/17/2005 PATRICIA GILBERT ENGINEERING REVIEW Approved
02/17/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied PREVIOUS COMMENTS NOT ADDRESSED
1. Show the water and waste piping on the floor plan.
2. Provide an upper terminal cleanout at the lavatory.
3. Show the sizes of the water piping.
4. Revise the water flow for the lavatory to comply
with ARS Title 45, Article 12, Section 45-313.
5. Show how the water heater is to be supported.
6. Provide maintenance access for the water heater.
Reference Section 511.2, UPC 1994.
7. The safety pan is not an approved location
for the termination of the temperature and pressure
relief valve. Reference Section 608.5, UPC 1994.
8. Clarify the termination point for the drain
from the safety pan; note #9 indicates a mop
sink but the water heater detail calls out a
"hub drain" located above the toilet room.
02/17/2005 JIM EGAN FIRE REVIEW Approved
02/17/2005 ROBERT SHERRY WATER REVIEW Approved
02/24/2005 TACHONG1 ZONING REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
02/24/2005 TAMI ACHONG OUT TO CUSTOMER Completed