| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/17/2005 | PATRICIA GILBERT | ENGINEERING | REVIEW | Approved | |
| 02/17/2005 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | PREVIOUS COMMENTS NOT ADDRESSED 1. Show the water and waste piping on the floor plan. 2. Provide an upper terminal cleanout at the lavatory. 3. Show the sizes of the water piping. 4. Revise the water flow for the lavatory to comply with ARS Title 45, Article 12, Section 45-313. 5. Show how the water heater is to be supported. 6. Provide maintenance access for the water heater. Reference Section 511.2, UPC 1994. 7. The safety pan is not an approved location for the termination of the temperature and pressure relief valve. Reference Section 608.5, UPC 1994. 8. Clarify the termination point for the drain from the safety pan; note #9 indicates a mop sink but the water heater detail calls out a "hub drain" located above the toilet room. |
| 02/17/2005 | JIM EGAN | FIRE | REVIEW | Approved | |
| 02/17/2005 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 02/24/2005 | TACHONG1 | ZONING | REVIEW | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 02/24/2005 | TAMI ACHONG | OUT TO CUSTOMER | Completed |