Permit Number: T05CM00048
Parcel: 10511061R

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T05CM00048
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/05/2005 PATRICIA GILBERT ENGINEERING REVIEW Approved
01/05/2005 DAN CASTRO ZONING REVIEW Approved
01/06/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Show the water and waste piping on the floor plan.
2. Provide an upper terminal cleanout at the lavatory.
3. Show the sizes of the water piping.
4. Revise the water flow for the lavatory to comply with ARS Title 45, Article 12, Section 45-313.
5. Show how the water heater is to be supported.
6. Provide maintenance access for the water heater. Reference Section 511.2, UPC 1994.
7. The safety pan is not an approved location for the termination of the temperature and pressure relief valve. Reference Section 608.5, UPC 1994.
8. Clarify the termination point for the drain from the safety pan; note #9 indicates a mop sink but the water heater detail calls out a "hub drain" located above the toilet room.
01/06/2005 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Needs Review
01/06/2005 ROBERT SHERRY WATER REVIEW Approved
01/06/2005 JIM EGAN FIRE REVIEW Approved
01/06/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
01/10/2005 LLESNY1 ELECTRICAL-COMMERCIAL REVIEW Needs Review
01/10/2005 LLESNY1 WWM REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
01/10/2005 LISA LESNY OUT TO CUSTOMER Completed