Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T05CM00017
Parcel: 117143190

Address:
541 S MAIN AV

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T05CM00017
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/27/2005 GERRY KOZIOL WWM REVIEW Denied needs to show public sewer & public sewer easement on site plan
05/02/2005 NEAL SAUNDERS BUILDING-RESIDENTIAL REVIEW Denied 1. Detail 4x8 beam connection to existing adobe wall.

2. Trusses are not provided for framing around chimney. Provide truss layout and appropriate girder trusses to match conditions on plans.

3. L1 in calcs call for (2) 6x 3-1/2x 5/16 steel while plans note use of existing lintels. Clarify.

4. Section R614 - Earthen Wall Structures; Bond beam does not meet prescriptive design. Comply with R614 or provide engineering for continous bond beam.

5.10/A9 - Provide gable end cross bracing.

Any questions contact Neil Saunders @ 791-5550 x1113.

Final Status

Task End Date Reviewer's Name Type of Review Description
05/05/2005 JMORALE1 OUT TO CUSTOMER Completed
05/05/2005 SUE REEVES REJECT SHELF Completed