Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T05CM00003
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/09/2005 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Denied | CITY OF TUCSON DEVELOPMENT SERVICES STRUCTURAL REVIEW COMMENTS DATE: 5/9/05 ACTIVITY NUMBER: T05CM00003 PROJECT NAME: Tattoo / Office PROJECT ADDRESS: 561 N. 4th Ave. ARCHITECT / ENGINEER: Susan Schaefer Kliman & M.K. Modi PROJECT REVIEWER: Christy Foreman TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL. PLEASE CALL AT 791-5550 X1108 OR EMAIL AT CFOREMA1@CI.TUCSON.AZ.US IF YOU CARE TO DISCUSS. 1) Accessibility into restroom see ANSI A117.1 - 2003, Fig. 404.2.3.1. Clarify / specify closer & latch. 2) Additional information required for wall section. Shows full section of two story space with top and bottom plate / channel connections. Clarify guardrail section per section 1012. |
| 05/10/2005 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Wet vents are limited to fixtures of only 1 and 2 fixture units each. Revise the drain piping as required. Reference Section 908.1, UPC 1994. |
| 05/10/2005 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 05/12/2005 | PATRICIA GEHLEN | ZONING | REVIEW | Denied | Zoning Building plans will be reviewed and approved once the site plan is approved. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 05/16/2005 | KMEDINA1 | OUT TO CUSTOMER | Completed |