Permit Number - T05CM00003
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/08/2005 MATT FLICK ENGINEERING REVIEW Passed No floodplain or significant engineering issues.
03/11/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved
03/17/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide calculations demonstrating adequate ventilation. Reference Section 401, IMC 2000.
2. Provide information to show that the termination of the restroom exhaust complies with the requirements of Section 401.5.2, IMC 2000.
3. Specify the minimum resistance (R-value) of the duct insulation to be used duct that is not exposed within the conditioned space. Reference Section 803.2.8, IECC 2000.
03/17/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Include the water demand for the mop sink in the water demand calculation. Reference Section 610.1, UPC 1994.
2. Calculate the water demand of items not specifically listed in Tables 6-3 or A-2 at their maximum demand but at not less than the fixture units for water supply outlets shown at the bottom of Table 6-3. Reference Section 610.3, UPC 1994.
3. One of the specified fixtures (espresso machine) may require a minimum pressure greater than the 20-PSI used in the water pipe sizing calculations. Confirm and revise calculations as necessary. Reference Section 608.1, UPC 1994.
4. The backflow preventer specified for the espresso machine (Conbraco model 40-400) is not approved for use with directly connected appliances that produce backpressure. Reference Table 6-1, UPC 1994.
5. Based on the provided calculations, the ¾" water supply to the building is unable to handle more than 11 fixture units. Reference Section A4.1, UPC 1994.
6. All storage-type water heaters require a listed expansion tank. Please show expansion tanks on plans. Reference Section 608.3, UPC 1994 with AZ State amendments.
7. If the specified water heater is not supplied with integral heat traps, provide heat traps (not bent flexible connectors) on the supply and discharge piping. Reference Section 804.4, IECC 2000.
8. Provide ½" insulation on the first eight feet of supply and discharge piping for the water heater. Reference Section 804.5, IECC 2000.
9. The specified lavatory faucets are designed for a flow rate of 2.2 GPM. According to ARS Title 45, Chapter 1, Article 12, the maximum flow rate for lavatory faucets shall be no more than an average of one-half gallon of water per minute at a pressure of eighty PSI or they shall be equipped with a mechanism that causes the faucet to close automatically after delivering no more than one-fourth gallon of water. Reference Section 402.1, UPC 1994, as amended by the State of Arizona.
10. Provide upper terminal cleanouts on horizontal drainage pipe over 5 feet in length (e.g. the branch with P-1A and P-4A). Reference Section 707.4, UPC 1994.
03/17/2005 ROBERT SHERRY WATER REVIEW Approved
03/23/2005 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Denied CITY OF TUCSON DEVELOPMENT SERVICES
STRUCTURAL REVIEW COMMENTS

DATE: 3/1/05
ACTIVITY NUMBER: T05CM00003
PROJECT NAME: Tattoo / Office
PROJECT ADDRESS: 561 N. 4th Ave.
ARCHITECT / ENGINEER: Paul Kilonzo Nzomo
PROJECT REVIEWER: Christy Foreman



TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1108 OR EMAIL AT CFOREMA1@CI.TUCSON.AZ.US IF YOU CARE TO DISCUSS.

1) Show all of building to clarify most restricted use to clarify / justify Nonseparated use or clarify separation between tenants for separated use.
2) Clarify what is 'M' occupancy.
3) Provide approved shop drawing for stairs.
4) Accessibility into restroom see ANSI A117.1 - 2003, Fig. 404.2.3.1.
5) Dimension accessibility for restroom clearance from reception desk to wall.
6) Dimension accessibility clearance into breakroom.
7) Clarify what is above breakroom piercing station.
8) Provide wall section for new partition walls.
03/29/2005 GERRY KOZIOL WWM REVIEW Approved
03/31/2005 PATRICIA GEHLEN ZONING REVIEW Denied Building plans will be reviewed and approved once the site plan is approved.

Final Status

Task End Date Reviewer's Name Type of Review Description
03/31/2005 DELMA ROBEY OUT TO CUSTOMER Completed