Permit Number - T05BU02828
Review Name: GRADING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/09/2006 TERRY STEVENS ZONING REVIEW Denied Grading notes for permits plus.
With TENTATIVE PLAT PLAN

01/09/06

Development Services Department
Zoning Review Section

Terry Stevens
Lead Planner

Comments:

1. The grading plan has been reviewed by Zoning Review Section but cannot approve the plan until it has been approved by the Engineering, and Landscape Review Sections and until all zoning comments or concerns have been addressed.

2. Zoning could not verify that the grading plan was in compliance with the approved tentative plat. Please submit one copy of the CDRC approved and stamped tentative plat, landscape, and NPPO plans with the next grading plan submittal.

3. Zoning will re-review the grading plan on the next submittal to insure compliance with the CDRC approved and stamped tentative plat. Additional comments may be forthcoming.
12/12/2005 ANDREW CONNOR NPPO REVIEW Denied Submit stamped approved tentative plat including the landscape plan, review will continue upon re-submittal.
12/22/2005 JOSE ORTIZ ENGINEERING REVIEW Denied To:Gregor and Grenier DATE: Dec 22, 2005
5232 E. Pima St FROM: Jose E. Ortiz
Tucson, Arizona 85712 Civil Engineer

SUBJECT: Third Street RCP-Grading Plan T04BU02828 (First Review)
T14S, R14E, Section 09

RESUBMITTAL REQUIRED: Grading Plan

The Grading Plan (GP) cannot be approved as submitted. Please address the following review comments prior to the next submittal.

Grading Plan:

1. Please include a response letter to the comments along with the corrected copies of the GP.
2. Add note: "Depress all landscaped areas a maximum of 6" for water harvesting"
3. A permit or a private improvement agreement will be necessary for any work performed within the Right-of-way. Contact Permits and Codes at (520) 791-5100 for permit information.
4. Verify that no off-site nuisance ponding takes place do to this development.
5. Confirm that the FFE of 77.77 is for all three lots.
6. Adjust Keynote callouts.
A. Sheet 2 Keynote descriptions 13, 18-21 are not in plan view, and keynotes 32, & 35 are not in keynote description
B. Sheet 3 Keynote 13 not in plan view.

If you have any questions, I can be reached at 791-5550 x1191 or jose.ortiz@tucsonaz.goz
Jose E. Ortiz
Civil Engineer
City of Tucson/Development Services Department
201 N. Stone Avenue
P.O. Box 27210
Tucson, Arizona 85726-7210
(520) 791-5550 x1191 office
(520) 879-8010 fax

Final Status

Task End Date Reviewer's Name Type of Review Description
01/10/2006 CINDY AGUILAR OUT TO CUSTOMER Completed
01/10/2006 SUE REEVES REJECT SHELF Completed