Review Details: GRADING

Permit Number - T05BU02544
Review Name: GRADING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/19/2005 ANDREW CONNOR NPPO REVIEW Denied According to the approved final plat this site is subject to the CITY OF TUCSON DEVELOPMENT STANDARD NO. 9-04.0 HILLSIDE DEVELOPMENT SITE IMPROVEMENT include the following notes to grading plan:

Vegetation Retention.

1. Existing trees with four (4) inch or greater trunk diameter and cacti will be preserved in their original locations, except for building sites and access and utilities serving building sites.

All plants designated to be preserved-in-place shall be retained at their existing grade during and after construction. Preservation fencing per DS 2-06. Figure 1 is required to be installed beyond the "drip-line" of the vegetation by one-half (½) the distance of the "drip-line" radius. DS 2-15.6.A

2. When retention of the above trees and cacti in their original locations is not possible due to building site location, the trees and cacti will be salvaged and replanted in areas requiring re-vegetation, whenever possible.

Re-vegetation. All disturbed areas including utility trenches or septic leaching fields which are not located in parking or driveway areas will be re-vegetated in compliance with the following requirements.

1. All plants used in re-vegetation must be the same as the native vegetation on the site or any adjacent site prior to grading or clearing. Include the proper and common name of new trees.

2. Re-vegetation will be accomplished with the following minimum requirements for plants.

a. Desert trees, a minimum of 15 gallon size with a minimum trunk diameter of two 2 inches measured at the soil level, or large specimen cactus will be placed at the same vegetation density found on the site prior to any clearing, grubbing, or grading.

b. Seeds for trees, desert shrubs, and grasses will be planted with a density adequate to control erosion and may use one of the following methods of planting or any other method approved by the Zoning Review Section at DSD.

Prior to any site disturbance a pre-grading inspection is required. Inspections may be scheduled by calling the IVR system at (520) 740-6970, inspection #09015 or by calling the Landscape Field Representative directly at 791-5640 Ext. 1140.
11/10/2005 DAVID RIVERA ZONING REVIEW Denied 11/10/05

Development Services Department
Zoning Review Section

David Rivera
Principal Planner

Comments:

1. The grading plan has been reviewed by Zoning Review Section but cannot approve the plan until it has been approved by the Engineering, and Landscape Review Sections and until all zoning comments or concerns have been addressed.

2. Zoning could not verify that the grading plan was in compliance with the approved site plan. Please submit two copies of the approved and stamped site, landscape, and NPPO plans with the next grading plan submittal.

3. Zoning will re-review the grading plan on the next submittal to insure compliance with the approved and stamped site plan. Additional comments may be forthcoming.

4. The limits of grading depicted on the site plan do not match the drawing as depicted on the approved tentative plat. ANy deviation from the approved tentative plat must be reviewed and approved by the Engineering section. See the engineering reviewer comments for specifics.
11/16/2005 PAUL MACHADO ENGINEERING REVIEW Denied To: Kim Kirschner DATE: November 18, 2005
Envision Corporation
2329 N. Tucson Blvd.
Tucson, Arizona 85716
SUBJECT: Pietruszynski Res. 4701 S Paseo Melodsio
Grading Plan T05BU02544 (First Review)
T14S, R15E, Section 36

RESUBMITTAL REQUIRED:Grading Plan and Drainage Statement.

The Grading Plan (GP) and Drainage Statement (DS) cannot be approved as submitted. Please address the following review comments prior to the next submittal.

Grading Plan:

1. Grading plan clearly marked "GRADING PLAN".
2. Please include a response letter to the comments along with the corrected copies of the GP.
3. On August 1, 2004, the new overlay zone procedures went into effect. All plans submitted after this date, which are in any overlay zone (i.e. SCZ, HDZ, ERZ, and W.A.S.H.), are required to go through the new procedure. Reference the applicable overlay zone in the general notes as required by D.S. 2-03.2.2.B.7. and submit an application for the overlay zone(s) that is/are applicable to this project. Contact Patricia Gehlen at 520-791-5550, Extension 1179 for additional information. Please be advised that as part of the overlay zone procedure, a public notification may be required.
4. List administrative address/site address on plans.
5. List GP number on plans.
6. Per a letter from the Engineer of the subdivision to the City of Tucson, dated September 20, 1996 and accepted by the City of Tucson, the areas of disturbance for lot 118 have been revised to "The build Area" as 0.40 Ac. The disturbed area shown on the plans was figured by inaccurately by scaling of the plans for review purposes. The scaled areas were within the limits of the proposed grading, but did not include any or the entire driveway. The area scaled is 23,400 sf. +/- or 054 Ac.+/-. This exceeds the area of the lot that can be disturbed. I am including a copy of the letter from the engineer of the subdivision with this submittal.
7. An HDZ review will be required for this parcel per L.U.C. Section 2.8.1.1. Contact
8. Special Grading Notes:
1. Show Gradeable area.
2. Show Average Cross slope Analysis (ACS).
3. Show limits of grading.
4. Show all slopes 15% of greater.
9. Show cross section with transverse and longitudinal slopes.
10. Please show the proposed roof drainage patterns, 100% of the 10-year flow must be conveyed under the sidewalks. Please provide supporting calculations to demonstrate compliance with D.S. 3-01.4.4. If the location(s) of the roof scuppers have not yet been decided, add a general note indicating sidewalk scuppers (per COT/SD) will be used when the roof scuppers locations have been designed.
11. Call out surface paving material.


Drainage Statement:
1. Please include a response letter to the comments along with the corrected copies of the DS.
2. A Drainage Statement is a brief description of drainage conditions applicable for a site which are not affected by 100 year flows of 100 cfs, of more……per S.M.D.D.F.M., chap. II, 2.1.2. The DS must be submitted along with the site plan and accepted with the approval of the grading plan.
3. The content and format of the Drainage Statement should follow S.M.D.D.F.M., chap. II, 2.2.
4. Show the project address or administration address on the cover sheet of the DS.

If you have any questions, I can be reached at 791-5550 x1193 or Paul.Machado@tucsonaz.gov
Paul P. Machado
Senior Engineering Associate
City of Tucson/Development Services Department
201 N. Stone Avenue
P.O. Box 27210
Tucson, Arizona 85726-7210
(520) 791-5550 x1193 office
(520) 879-8010 fax
C:/4701 S PASEO MELODIOSO GRAD

Final Status

Task End Date Reviewer's Name Type of Review Description
11/22/2005 GBONILL1 OUT TO CUSTOMER Completed
11/22/2005 SUE REEVES REJECT SHELF Completed