Permit Number: T05BU02434
Parcel: 124090290

Address:
230 N WARREN AV

Review Status: Completed

Review Details: WALLS

Permit Number - T05BU02434
Review Name: WALLS
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/03/2005 PATRICIA GILBERT ENGINEERING REVIEW Denied DATE: November 3, 2005
ACTIVITY NUMBER: T05OT02495 / T05BU02434
PROJECT NAME: Anthony Colson Wall Design
PROJECT ADDRESS: 230 North Warren Avenue
PROJECT REVIEWER: Patricia Gilbert

FLOODPLAIN USE PERMIT IS DENIED

RESUBMITTAL REQUIRED: SITE PLAN, FLOODPLAIN USE PERMIT APPLICATION

SUBMIT: HYDROLOGY REPORT, OVERLAY ZONE APPLICATION TO THE COMMUNITY DESIGN REVIEW COMMITTEE (CDRC) OFFICE (Please contact Patricia Gehlen, CDRC Manager, for further submittal requirements).


1. The proposed wall is within High School Wash which is regulated wash under the provisions of Chapter 29, Article VIII, Watercourse Amenities, Safety and Habitat. A separate overlay review process must take place simultaneously with this review. Contact Patricia Gehlen, 791-5550 extension 1179, for submittal requirements. The overlay submittal must be processed through the CDRC office. Please refer to the submitted Overlay zone application and procedure process document.

2. The proposed wall is within a FEMA Flood Hazard Area Zone AE. A hydrology report is required to be submitted when development occurs within a flood hazard area. Refer to the Standards Manual for Drainage Design and Floodplain Management 2.3 for report format and content.
11/04/2005 MICHAEL ST. PAUL ZONING REVIEW Denied CDRC TRANSMITTAL

FROM: Michael St.Paul FOR: David Rivera
Planner Technician Principal Planner

PROJECT:
T05BU02434
230 North Warren Avenue
retaining wall > 10'
TRANSMITTAL: November 4, 2005

COMMENTS: Please attach a response letter with the next submittal, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.
CODE SECTION/
DEVELOPMENT
STANDARD

1. Please provide a copy of the last approved site plan depicting all structures.
2003 IRC: R106.2
2. It appears that portions of the retaining wall with the wall or fence on top exceed the feet (10') in height. Please provide dimensioned wall sections that clearly depict the ground level and the wall heights.
LUC Sec 3.2.5.2.H.2
11/14/2005 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Denied DATE: November 3, 2005
ACTIVITY NUMBER: T05OT02495 / T05BU02434
PROJECT NAME: Anthony Colson Wall Design
PROJECT ADDRESS: 230 North Warren Avenue
PROJECT REVIEWER: CHRISTY FOREMAN

1) PROVIDE STRUCTURAL CALCULATIONS JUSTIFYING REINFORCEMENT / DESIGN OF RETAINING WALL PER CHAPT. 16 OF IBC 2003. PROVIDE SOILS REPORT IF NECESSARY PER STRUCTURAL CALCULATIONS.

2) CLARIFY LOCATION OF DEMOLITION OF EXISTING WALL.

3) PROVIDE WALL SECTIONS FOR EACH SPECIFIED DESIGN. CLARIFY LOCATION OF WALL SECTIONS ON DRAWINGS.

4) SPECIAL INSPECTION FORMS WILL BE REQUIRED AS SPECIFIED PER STRUCTURAL ENGINEER BEFORE PERMIT CAN BE ISSUED.

Final Status

Task End Date Reviewer's Name Type of Review Description
11/23/2005 DELMA ROBEY REJECT SHELF Completed