Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T05BU02343
Parcel: 11446213B

Review Status: Completed

Review Details: GRADING

Permit Number - T05BU02343
Review Name: GRADING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/30/2005 JOE LINVILLE NPPO REVIEW Denied Submit the approved development plan/landscape plan. The grading plan will be reviewed for conformance with the approved plans upon resubmittal.
10/21/2005 DAVID RIVERA ZONING REVIEW Denied 10/21/05

Development Services Department
Zoning Review Section

David Rivera
Principal Planner

Comments:

1. The grading plan has been reviewed by Zoning Review Section but cannot approve the plan until it has been approved by the Engineering, and Landscape Review Sections and until all zoning comments or concerns have been addressed.

2. Zoning could not verify that the grading plan was in compliance with the approved development plan. Please submit two copies of the approved and stamped development, landscape, and NPPO plans with the next grading plan submittal.

3. Zoning will re-review the grading plan on the next submittal to insure compliance with the approved site/development plan. Additional comments may be forthcoming.

4. A site card with DSD approvals by Fire, Zoning, Handi-cap, Engineering, and Landscape/NPPO including the approved development plan stamped for site plan approval and signatures is required before the grading plan can be approved by Zoning. Two copies of the approved development plan, landscape and NPPO plans are to be submitted with the grading plans packet for processing and approval as a site plan. No fees are involved in re-stamping the development/tentative plat plans as an approved site plan. The development plan may be walked through for stamps and site card sign off. Submit the following: two copies of the stamped development plan, landscape and NPPO plans must be included with the grading plans packet processed together for site approval.
10/28/2005 PAUL MACHADO ENGINEERING REVIEW Denied To: Jim Watson DATE: October 27, 2005
Architect, PLC
Tucson, Arizona 85716
SUBJECT: Desert Link, 2478 N. Country Club Drive
Grading Plan T05BU023432 (First review)
T15S, R13E, Section 32

RESUBMITTAL REQUIRED: Grading Plan, Drainage Report and SWPPP

The Grading Plan (GP), Drainage Report (DR) and Stormwater Pollution Prevention Plan cannot be approved as submitted. Please address the following review comments prior to the next submittal.

Grading Plan:
1. Please include a response letter to the comments along with the corrected copies of the GP.
2. Include 4 copies of the GP.
3. The GP cannot be approved prior the approval of the development plan.
4. As per the Federal ADA requirements, all wheel chair ramps shall have the truncated domes instead of the standard grooves that are shown on COT SD 207. Aside from the Truncated Domes, all wheel chair ramps shall be constructed in accordance with COT SD 207.
5. Label existing and future sight visibility triangles per D.S. 2-02.2.1.10. The SVT's are not shown correctly. Revise as required.
6. Add to general notes: All grading shall conform to D.S. 11.0.
7. Add note: "Depress all landscaped areas a maximum of 6" for water harvesting"
8. Add the basin(s) maintenance responsibility note per S.M.D.D.F.M. 2.3.1.6 C 1 and 2 to the GP.
9. List administrative address/site address on plans.
10. Provide a wheelchair ramp for the sidewalk at the NW corner of the project. Also, the existing WC ramp at the South end of the property must be brought up to current City of Tucson standands.
11. A permit or a private improvement agreement will be necessary for any work performed within the Right-of-way. Contact Permits and Codes at (520) 791-5100 for permit information.






Drainage report:
1. The DR has been accepted by the Engineering Division.

Stormwater pollution prevention plan:
1. The SWPPP has been accepted by the Engineering Division.
2. Submit the three copies of the previously submitted SWPPP with the next submittal if the GP.

If you have any questions, I can be reached at 791-5550 x1193 or Paul.Machado@tucsonaz.gov
Paul P. Machado
Senior Engineering Associate
City of Tucson/Development Services Department
201 N. Stone Avenue
P.O. Box 27210
Tucson, Arizona 85726-7210
(520) 791-5550 x1193 office
(520) 879-8010 fax
C:/2478 N DESERT LINKS DR Grad

Final Status

Task End Date Reviewer's Name Type of Review Description
11/01/2005 DELMA ROBEY OUT TO CUSTOMER Completed