Permit Number: T05BU02343
Parcel: 11446213B

Review Status: Completed

Review Details: RESUBMITTAL - GRADING ALL

Permit Number - T05BU02343
Review Name: RESUBMITTAL - GRADING ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/16/2006 DAVID RIVERA ZONING REVIEW Denied 01/16/06

Development Services Department
Zoning Review Section

David Rivera
Principal Planner

Comments:

1. The grading plan has been reviewed by Zoning Review Section but cannot approve the plan until it has been approved by the Engineering Review Section and until all zoning comments have been addressed.

2. I acknowledge that two copies of the CDRC approved and stampded sets of development, landscape, and NPPO plan sheets have ben included with the grading plan. What has not been done is to process the development plan as a site plan. Please apply for a site permit card and have the approved sets of the DP, LS, and NPPO plan sheets rubber stamped as a site plan. Zoning is willing to review and approve the grading plan over the counter once the Engineering Reviewer has approved it. If the the applicant wishes to do this please call me and set up a time to have the grading plan reviewed over the counter, (with engineering approval).

Previous Coment: A site card with DSD approvals by Fire, Zoning, Handi-cap, Engineering, and Landscape/NPPO including the approved development plan stamped for site plan approval and signatures is required before the grading plan can be approved by Zoning. Two copies of the approved development plan, landscape and NPPO plans are to be submitted with the grading plans packet for processing and approval as a site plan. No fees are involved in re-stamping the development/tentative plat plans as an approved site plan. The development plan may be walked through for stamps and site card sign off. Submit the following: two copies of the stamped development plan, landscape and NPPO plans must be included with the grading plans packet processed together for site approval.
12/14/2005 PAUL MACHADO ENGINEERING REVIEW Denied To: Jim Watson DATE: December 15, 2005
Architect, PLC
3026 N. Country Club Road
Tucson, Arizona 85716
SUBJECT: Desert Link, 2478 N. Country Club Drive
Grading Plan T05BU023432 (Second review)
T15S, R13E, Section 32

RESUBMITTAL REQUIRED: Grading Plan, Drainage Report and SWPPP

The Grading Plan (GP) cannot be approved as submitted. Please address the following review comments prior to the next submittal. Re-submit the Drainage Report (DR) and Stormwater Pollution Prevention Plan (previously approved) along the re-submittal of the GP.

Grading Plan:
1. Please include a response letter to the comments along with the corrected copies of the GP.
2. As per the Federal ADA requirements, all wheel chair ramps shall have the truncated domes instead of the standard grooves that are shown on COT SD 207. Aside from the Truncated Domes, all wheel chair ramps shall be constructed in accordance with COT SD 207.
3. Label existing and future sight visibility triangles per D.S. 2-02.2.1.10. The SVT's are not shown correctly. Revise as required. See redlines.
4. Provide a wheelchair ramp for the sidewalk at the NW corner of the project. Also, the existing WC ramp at the South end of the property must be brought up to current City of Tucson standards. Adding truncated domes to the existing wheelchair ramp does not constitute as being brought up to standards. The wheel chair ramp must be re-constructed to present City of Tucson standards. A wheelchair ramp shall be installed at the corner of Super Chicken Dr and Desert Links Dr. Per previous comments.

Drainage report:
1. The DR has been accepted by the Engineering Division.
2. Submit the three copies of the previously submitted DR with the next submittal of the GP.
Stormwater pollution prevention plan:

1. The SWPPP has been accepted by the Engineering Division.
2. Submit the three copies of the previously submitted SWPPP with the next submittal of the GP.

If you have any questions, I can be reached at 791-5550 x1193 or Paul.Machado@tucsonaz.gov
Paul P. Machado
Senior Engineering Associate
City of Tucson/Development Services Department
201 N. Stone Avenue
P.O. Box 27210
Tucson, Arizona 85726-7210
(520) 791-5550 x1193 office
(520) 879-8010 fax
C:/2478 N DESERT LINKS DR Grad2
12/19/2005 ANDREW CONNOR NPPO REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
01/18/2006 DELMA ROBEY OUT TO CUSTOMER Completed
01/18/2006 SUE REEVES REJECT SHELF Completed