Permit Number: T05BU02264
Parcel: 133033080

Review Status: Completed

Review Details: RESUBMITTAL - GRADING ALL

Permit Number - T05BU02264
Review Name: RESUBMITTAL - GRADING ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/08/2006 PAUL MACHADO ENGINEERING REVIEW Denied To: Gerardo Calza, P.E. DATE: February 14, 2006
Urban Engineering
877 S. Alvernon Way
Tucson, Arizona 85711
SUBJECT: Paving and Grading for 1475 N. Houghton Road
Grading Plan T05BU02264 (Third Review)
T14S, R15E, Section 02

RESUBMITTAL REQUIRED: Grading and Paving Plan.

The Grading Plan (GP) and Drainage Statement (DS) cannot be approved as submitted. Please address the following review comments prior to the next submittal.

Grading Plan:

1. Please include a response letter to the comments along with the corrected copies of the GP.
2. Upon a recent field visit the debris placed at the edge of Aqua Caliente Wash can not be considered bank protection. Remove all references to the "Bank Protection" on the improvement plans. The erosion hazard setback may remain if in fact that is the top of bank.

Drainage Statement:
1. Please include a response letter to the comments along with the corrected copies of the DS.
2. Upon a recent field visit the debris placed at the edge of Aqua Caliente Wash can not be considered bank protection. Remove all references to the "Bank Protection" in the DS. The erosion hazard setback may remain if in fact that is the top of bank.

If you have any questions, I can be reached at 791-5550 x1193 or Paul.Machado@tucsonaz.gov
Paul P. Machado
Senior Engineering Associate
City of Tucson/Development Services Department
201 N. Stone Avenue
P.O. Box 27210
Tucson, Arizona 85726-7210
(520) 791-5550 x1193 office
(520) 879-8010 fax
C:/1475 N. Houghton Rd Grad3
02/15/2006 ANDREW CONNOR NPPO REVIEW Denied 1. Applicants proposing a project with encroachment into the one hundred (100) year floodplain are required to submit a mitigation plan in accordance with Sec. 2.8.6.5.D of the LUC and an Environmental Resource Report as defined in Sec. 6.2.5 of the LUC. Additionally compliance with regulations in accordance with the DSD - Full Notice Procedure, Sec.23A-50 and 23A-51. (Ord. No. 9967, ยง2, 7/1/04), are required. Contact Patricia Gehlen EXT 1179 or via e-mail at Patricia.Gahlen@tucsonaz.gov for questions and assistance with the review process.
03/01/2006 DAVID RIVERA ZONING REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
03/01/2006 GBONILL1 OUT TO CUSTOMER Completed
03/01/2006 SUE REEVES REJECT SHELF Completed