Permit Number: T05BU02244
Parcel: 13219015B

Address:
2200 E BENSON HY

Review Status: Completed

Review Details: GRADING

Permit Number - T05BU02244
Review Name: GRADING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/16/2005 ANDREW CONNOR NPPO REVIEW Denied Site plan approval is necessary to continue review.
09/29/2005 DAN CASTRO ZONING REVIEW Denied Grading plan may not be approved prior to Engineering and Landscape approval.
09/29/2005 PAUL MACHADO ENGINEERING REVIEW Denied To: Thomas Panno DATE: September 30, 2005
Architects 8042 E. Hayden Place
Tucson, Arizona 85715

SUBJECT: 2200 E. Benson Hwy., Caylor Industrial
Grading Plan T05bu02244 (First Review)
T14S, R14E, Section 32

RESUBMITTAL REQUIRED: Grading Plan.

The Grading Plan (GP) cannot be approved as submitted. Please address the following review comments prior to the next submittal.

Grading Plan:
1. Please include a response letter to the comments along with the corrected copies of the GP.
2. As per the Federal ADA requirements, all wheel chair ramps shall have the truncated domes instead of the standard grooves that are shown on COT SD 207. Aside from the Truncated Domes, all wheel chair ramps shall be constructed in accordance with COT SD 207. This requirement is for all wheelchair ramps required of the project.
3. Add note: "Depress all landscaped areas a maximum of 6" for water harvesting"
4. Include a detail of the trash enclosure.
5. Label existing and future sight visibility triangles.
6. There is a conflict with note no. 20 and the Drainage Report.
7. Show both sides of the entrance with 25' radius and wheelchair ramp.
8. List Site Plan number on the GP.
9. Call out surface paving material.
10. Show details of all surface materials.
11. A permit or a private improvement agreement will be necessary for any work performed within the Right-of-way. Contact Permits and Codes at (520) 791-5100 for permit information.
12. Call out peak discharges entering and exiting the site.




13. Detention/Retention basin:
· Match Drainage report.
· Cross-sections and dimension.
· Water surface elevations.
· Peak discharge at basin's outlet.

Drainage report:
1. The DR has been conditionally accepted by engineering.
2. Show a cross-section and a detail of the Det./Ret. basin.

If you have any questions, I can be reached at 791-5550 x1193 or Paul.Machado@tucsonaz.gov
Paul P. Machado
Senior Engineering Associate
City of Tucson/Development Services Department
201 N. Stone Avenue
P.O. Box 27210
Tucson, Arizona 85726-7210
(520) 791-5550 x1193 office
(520) 879-8010 fax
2200 E Benson Hwy Grad