Permit Number: T05BU02219
Parcel: 116277610

Review Status: Completed

Review Details: RESUBMITTAL - GRADING ALL

Permit Number - T05BU02219
Review Name: RESUBMITTAL - GRADING ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/28/2005 ANDREW CONNOR NPPO REVIEW Approv-Cond
11/28/2005 MICHAEL ST. PAUL ZONING REVIEW Approved
12/21/2005 ELIZABETH EBERBACH ENGINEERING REVIEW Approved TO: Alan Roberts, RA
SUBJECT: 3224 W TUMAMOC DR Grading Resubmittal Review
LOCATION: T14S, R13E, Section 17
REVIEWER: Elizabeth Eberbach
ACTIVITY NUMBER: T05BU02219, T05CM01969

Summary: Engineering Division has reviewed the resubmittal, and recommends approval of the grading plan. The following conditions will be added to the grading permit:

GRADING PERMIT CONDITIONS:
1) Call for Pre-construction meeting. For a DSD Engineering Inspection, call IVR (740-6970), or schedule with a Customer Service Representative at the Development Services Department, or contact DSD Engineering at 791-5550 extension 2101, or schedule inspections online at: http://www.ci.tucson.az.us/dsd/Online_Services/Online_Permits/online_permits.html
2) Any revision to the actual disturbance area as identified on the grading limits shall be approved by Landscaping and Engineering Inspectors. This includes any areas proposed for construction staging area, or construction materials, or vehicle parking.
3) Any revision to the Grading Plan may require a re-submittal of a revised grading plan for review. Contact DSD Engineering at 791-5550 to discuss changes in grading design.
4) Heavy duty construction fence shall be installed along east side of grading limits.
5) Minimum 2' setback from property line to grading limits shall be maintained.
6) Slopes shall be no steeper than 2:1(H:V).
7) Estimates for cut and fill quantities were received by the registrant by phone 22DEC05: 400yds Cut, 400 yds Fill.
8) All slopes with riprap shall have filter fabric, or as specified by a geotechnical report.
9) If grading construction is expected to last longer than the expiration date of the grading permit, contact DSD to renew/extend the Grading Permit. If Final Grading Inspection has not been completed before the Grading Permit expires, and the permit has not been renewed, additional fees and reviews may be required.
10) A copy of the Grading Plan, Grading Permit, and any Geotechnical Reports shall be kept at the site at all times, until final grading approval.

I can be reached at 791-5550, ext.2204 if you have questions.

Elizabeth Eberbach, PE
Civil Engineer
Engineering Division
Development Services Department

Final Status

Task End Date Reviewer's Name Type of Review Description
12/27/2005 SUE REEVES OUT TO CUSTOMER Completed