Permit Number: T05BU02200
Parcel: 12409156A

Review Status: Completed

Review Details: GRADING

Permit Number - T05BU02200
Review Name: GRADING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/13/2005 PATRICIA GILBERT ENGINEERING REVIEW Denied DATE: September 13, 2005
ACTIVITY NUMBER: T05BU02200
PROJECT NAME: Starbucks Coffee
PROJECT ADDRESS: 1821 East Broadway Blvd.
PROJECT REVIEWER: Patricia Gilbert

The following items must be revised or added to the grading plan. Please include a response letter with the next submittal that states how all comments have been addressed.

RESUBMITTAL REQUIRED: GRADING PLAN

1. A copy of the stamped approved Site Plan must be included with the Grading Plan submittal.

2. Indicate on the grading plan the area of disturbance. Construction disturbance of over an acre requires submittal of a Stormwater Pollution Prevention Plan (SWPPP).

3. Sheet C-1 indicates in section A that the alley is to remain existing. Are any improvements occurring offsite in the alley? Are improvements occurring where the vehicles are egressing from the site to the alley?

4. Indicate the height of the walls shown in detail section A and B on sheet C-1.

5. There appears to be a wall depicted in the landscape border along Campbell Ave and Broadway Blvd., is this a correct assumption? If this is a wall call out on the plan and indicate the height.
09/15/2005 ANDREW CONNOR NPPO REVIEW Approved
10/03/2005 CAGUILA1 ZONING REVIEW Needs Review