Permit Number: T05BU02167
Parcel: 110121020

Review Status: Completed

Review Details: RESUBMITTAL - GRADING ALL

Permit Number - T05BU02167
Review Name: RESUBMITTAL - GRADING ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/05/2008 PAUL MACHADO ENGINEERING REVIEW Denied To: Gervasio and Assoc. Inc. DATE: March 5, 2008 Joesph Gervasio, P.E.
77 E. Thomas Road, Ste. 120
Phoenix, Arizona 85012
SUBJECT: Tucson Senior Living, 2675 N. Wyatt Road
Grading Plan T05BU02167 (Third Review)
T14S, R15E, Section 28

RESUBMITTAL REQUIRED: Floodplain Use permit (FUP).

Grading Plan:
1. Please include a response letter to the comments along with the corrected copies of the GP.
2. A flood plain use permit is required prior to the approval of the grading plan. The FUP must be submitted along with or prior to approval of the Grading plan. Per previous comment.
3. Resubmit the Grading plan package with the FUP.

Drainage Statement:
1. The previous DS has been accepted by engineering.
2. The DS and Geo. Tech. report do not have to be resubmitted with the Grading plan and FUP.

If you have any questions, I can be reached at 837-4932 or Paul.Machado@tucsonaz.gov
Paul P. Machado
Senior Engineering Associate
City of Tucson/Development Services Department
201 N. Stone Avenue
P.O. Box 27210
Tucson, Arizona 85726-7210
(520) 837-4932 office
(520) 879-8010 fax
C:\2675 N. Wyatt Dr. Grad 3
03/10/2008 ANDREW CONNOR NPPO REVIEW Denied Submit stamped approved landscape and NPP plans included with development plan, review will continue upon re-submittal of requested documents.
03/25/2008 CAGUILA1 ZONING REVIEW Needs Review