Permit Number: T05BU02167
Parcel: 110121020

Review Status: Completed

Review Details: RESUBMITTAL - GRADING ALL

Permit Number - T05BU02167
Review Name: RESUBMITTAL - GRADING ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/16/2006 DAVID RIVERA ZONING REVIEW Denied 1/16/06

Development Services Department
Zoning Review Section

David Rivera
Principal Planner

Comments:

1. The grading plan has been reviewed by Zoning Review Section but cannot approve the plan until it has been approved by the Engineering, and Landscape Review Sections and until all zoning comments or concerns have been addressed.

2. Zoning will re-review the grading plan on the next submittal to insure compliance with the approved and stamped site plan. Additional comments may be forthcoming.
12/15/2005 PAUL MACHADO ENGINEERING REVIEW Denied To: Gervasio and Assoc. Inc. DATE: December 19, 2005
Joesph Gervasio, P.E. 77 E. Thomas Road, Ste. 120 Phoenix, Arizona 85012
SUBJECT: Tucson Senior Living, 2675 N. Wyatt Road
Grading Plan T05BU02167 (Second Review)
T14S, R15E, Section 28

RESUBMITTAL REQUIRED: Grading Plan and Drainage Statement.

The Grading Plan (GP) and Drainage Statement (DS) cannot be approved as submitted. Please address the following review comments prior to the next submittal.

Grading Plan:
1. Please include a response letter to the comments along with the corrected copies of the GP.
2. A flood plain use permit is required prior to the approval of the grading plan.
3. As per the Federal ADA requirements, all wheel chair ramps shall have the truncated domes instead of the standard grooves that are shown on COT SD 207. Aside from the Truncated Domes, all wheel chair ramps shall be constructed in accordance with COT SD 207.
4. Correct or edit G&A General note 12 to reflect comment no. 15.
5. Include the Soils report for review on the next submittal per G&A Grading and Drainage note no. 1.
6. Correct or edit G&A Grading and Drainage note 9 and 10. Remove the reference to M.A.G.
7. Correct or edit City of Tucson: Standard Paving & Grading notes no 2: Please provide existing topographic contours at intervals not exceeding two (2) feet and/or spot elevations as pertinent and Bench Mark based on City of Tucson Datum, including City Field Book and page number per D.S. 2-02.2.1.23.
8. Correct or edit City of Tucson: Standard Paving & Grading notes no 3 and 7: All grading shall conform to City of Tucson Development Standards 11.0.
9. Correct or edit City of Tucson: Standard Paving & Grading notes no 15: The City of Tucson does not issue type I or II grading permits. The note shall be removed.
10. Correct the legal description. The Bk. and Pg. used in the legal description is for a different subdivision to the west.
11. Add note: "Depress all landscaped areas a maximum of 6" for water harvesting"
12. Add the basin(s) maintenance responsibility note per S.M.D.D.F.M. 2.3.1.6 C 1 and 2 to the GP.
13. List Site Plan number on the plans.
14. Show Phase numbers and delineate. Each phase must function independent of future phases.
15. Please show the proposed roof drainage patterns, 100% of the 10-year flow must be conveyed under the sidewalks. Please provide supporting calculations to demonstrate compliance with D.S. 3-01.4.4. If the location(s) of the roof scuppers have not yet been decided, add a general note indicating sidewalk scuppers (per COT/SD) will be used when the roof scuppers locations have been designed.
16. Show details of all surface materials.
17. A permit or a private improvement agreement will be necessary for any work performed within the Right-of-way. Contact Permits and Codes at (520) 791-5100 for permit information.
18. Delineate 100-year W.S.E.L., Floodplain and erosion hazard setback.
19. Show the 100-year flood peak discharge.
20. Drainage patterns with percent slopes (Show patterns within the first 100 feet from the property line).
21. Flow arrows, grades and flow rates within and adjacent to site to show drainage scheme.
22. Call out peak discharges entering and exiting the site.
23. The proposed grading for the phase II is 0.8 acres, which is under the 1.0 acre SWPPP requirement. However, the proximity of the project to the FEMA mapped floodplain and because of the proposed grading of the existing basins that drain directly into the Arcadia Wash a: "A Stormwater Pollution Prevention Plans (SWPPP's) will be required for this project. Submit 3 sets of the grading and SWPPP's with text, upon completion and submittal of a grading permit application. A grading permit may not be issued prior to site plan approval. Subsequent comments may be necessary, depending upon the nature and extent of revisions that occur to the plans".

Drainage Statement:
1. Please include a response letter to the comments along with the corrected copies of the DS.
2. Explain in the DS how the FFE was determined, if the FFE was determined by a previous DR, then a statement in the DS must added that you have reviewed and agree with the data from the previous DR.
3. The content and format of the Drainage Statement should follow S.M.D.D.F.M., chap. II, 2.2.
4. Show the project address or administration address on the cover sheet of the DS.
5. If applicable, add the basin(s) maintenance responsibility note and checklist per S.M.D.D.F.M. 2.3.1.6 C 1 and 2 to the DS.

If you have any questions, I can be reached at 791-5550 x1193 or Paul.Machado@tucsonaz.gov
Paul P. Machado
Senior Engineering Associate
City of Tucson/Development Services Department
201 N. Stone Avenue
P.O. Box 27210
Tucson, Arizona 85726-7210
(520) 791-5550 x1193 office
(520) 879-8010 fax
C:\2675 N. Wyatt Dr. Grad2
12/21/2005 ANDREW CONNOR NPPO REVIEW Denied Submit stamped approved landscape and NPP plans included with development plan, review will continue upon re-submittal of requested documents.

Final Status

Task End Date Reviewer's Name Type of Review Description
01/31/2006 GBONILL1 OUT TO CUSTOMER Completed
01/31/2006 SUE REEVES REJECT SHELF Completed