Permit Number: T05BU01997
Parcel: 116277580

Review Status: Completed

Review Details: GRADING

Permit Number - T05BU01997
Review Name: GRADING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/25/2005 ANDREW CONNOR NPPO REVIEW Denied 1. According to approved tentative plat, prior to development of lots 1-23 Coyote Pass. A Native Plant Preservation Plan must be submitted and approved by the City of Tucson. If lot has been previously disturbed than application for exception must be included with re-submittal.
09/17/2005 DAVID RIVERA ZONING REVIEW Denied 09/17/05

Development Services Department
Zoning Review Section

David Rivera
Principal Planner

Comments:

1. The grading plan has been reviewed by Zoning Review Section but cannot approve the plan until it has been approved by the Engineering, and Landscape Review Sections and until all zoning comments or concerns have been addressed.

2. Zoning could not verify that the grading plan was in compliance with the approved site plan. Please submit two copies of the approved and stamped site, landscape, and NPPO plans with the next grading plan submittal.

3. Zoning will re-review the grading plan on the next submittal to insure compliance with the approved and stamped site plan. Additional comments may be forthcoming.

4. The plan has been reviewed for grading compliance only. A separate review and approval for a building permit will be required. Please indicate on the grading plan if this is one of the barrier free lots. If so indicate on the plan how accessibility will be provided from the street sidewalk to the front door. The maximum slope allowed is 1:12. Demonstrate on the plan compliance this requirement.
09/19/2005 ELIZABETH EBERBACH ENGINEERING REVIEW Denied TO: DUCATI / ROGERS
SUBJECT: 3276 W TUMAMOC DR Grading Review
LOCATION: T14S, R13E, Section 17
REVIEWER: Elizabeth Eberbach
ACTIVITY NUMBER: T05BU01997

Summary: Engineering Division has reviewed the resubmitted items, and may not recommend approval at this time. Please provide three copies of the revised grading plan addressing the comments provided below.

GRADING PLAN COMMENTS:
1) Tucson Code Sec.26-2: The proposed ramada structure does not conform to the erosion hazard setback indicated on the plan. The structure must be setback for the erosion hazard area.
2) Show all linework as shown within the lot boundary as depicted on the Final Plat, including the delineation of the 20' private utility and private drainage easement, and the 10' public utility easement.
3) Revise grading limits to provide for disturbance area for construction area, and update note for square footage of disturbance.
4) DS Sec 9-04.3: Show compliance for this section of the HDZ standards. Provide the following data on the plan:
a) Provide existing / proposed contour lines
b) Show that there is no fill or encroachment into the drainage easement
c) Label all slopes steeper than 3:1(H:V) with riprap and filter fabric or as specified by the geotechnical report
d) Label all slopes 3:1(H:V) or less steep and label as revegetation with native plants
e) For any retaining systems, label top & bottom of wall elevations on the plan
f) Add a general note stating that the lot conforms to Hillside Development Zone (HDZ) requirements: DS Sec.9-04.3.
5) Revise notes 4, 6, and 7 to reference the City of Tucson (DS Sec.11-01: grading standards).

I can be reached at 791-5550, ext.2204 if you have questions.

Elizabeth Eberbach, PE
Civil Engineer
Engineering Division
Development Services Department

Final Status

Task End Date Reviewer's Name Type of Review Description
09/23/2005 JMORALE1 OUT TO CUSTOMER Completed
09/23/2005 SUE REEVES REJECT SHELF Completed